TeSys U standard control unit to be inserted in power bases LUB32, LUB32, LUB38 to form a TeSys U starter controller, for 3-phase motor applications up to 7.5kW@400V. It provides full protection to motors with a rated current Ir 4.5-18A (Ir adjustable), overload tripping class 10, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). To be used with a 110-240V AC / 110-220V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Add to Quote CataloguePart Number | LUCA18FU |
---|---|
Country of Origin | FR |
UPC | 785901221944 |
UPC11 | 78590122194 |
EAN | 3389110364040 |
Availability | S |
Lead Time | 3 |
UNSPSC | 39121521 |
ECCN | EAR99 |
HTs Code | 8536304000 |
RoHS Compliant | Yes |
Discount Schedule | I11 |
Return Indicator | Yes |
Depth | 2.36 inch |
Height | 2.60 inch |
Width | 1.77 inch |
Weight | 0.30 pound |
Range Of Product | TeSys U |
---|---|
Range | TeSys |
Product Name | TeSys U |
Device Short Name | LUCA |
Product Or Component Type | Standard control unit |
Device Application | Motor control Motor protection |
Product Specific Application | Basic protection requirements for motor starters: overload and short-circuit |
Main Function Available | Earth fault protection Manual reset Protection against phase failure and phase imbalance Protection against overload and short-circuit |
Product Compatibility | Power base LUB32 Power base LUB38 Power base LUB320 Power base LUB380 Reversing contactor breaker LU2B32FU Reversing contactor breaker LU2B38FU |
Ue Rated Operational Voltage | 690 V AC |
Network Frequency | 40...60 Hz |
Load Type | 3-phase motor self-cooled |
Utilisation Category | AC-41 AC-44 AC-43 |
Motor Power kW | 7.5 kW 400...440 V AC 50/60 Hz 9 kW 500 V AC 50/60 Hz 15 kW 690 V AC 50/60 Hz |
Rated Motor Current Adjustment Range | 4.5…18 A |
Thermal Overload Class | Class 10 40…60 Hz -13…158 °F (-25…70 °C) IEC 60947-6-2 Class 10 40…60 Hz -13…158 °F (-25…70 °C) UL 508 |
Tripping Threshold | 14.2 x Ir +/- 20 % |
Phase Failure Sensitivity | Yes |
[Uc] Control Circuit Voltage | 110...240 V AC 110...220 V DC |
Ctrl Circuit Voltage Limits | 88...264 V AC 110...240 V in operation 88...242 V DC 110...220 V in operation 55 V AC 110...240 V drop-out 55 V DC 110...220 V drop-out |
Typical Current Consumption | 280 mA 110...240 V AC I maximum while closing with LUB32 280 mA 110...240 V AC I maximum while closing with LUB38 280 mA 110...220 V DC I maximum while closing with LUB32 280 mA 110...220 V DC I maximum while closing with LUB38 25 mA 110...240 V AC I rms sealed with LUB32 25 mA 110...240 V AC I rms sealed with LUB38 25 mA 110...220 V DC I rms sealed with LUB32 25 mA 110...220 V DC I rms sealed with LUB38 |
Heat Dissipation | 3 W control circuit with LUB32 3 W control circuit with LUB38 |
Operating Time | 35 ms opening with LUB32 control circuit 35 ms opening with LUB38 control circuit 50 ms closing with LUB32 control circuit 50 ms closing with LUB38 control circuit |
Standards | EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier |
Product Certifications | CE UL CSA CCC EAC ASEFA ATEX Marine |
Ui Rated Insulation Voltage | 690 V IEC 60947-6-2 600 V UL 60947-4-1 600 V CSA C22.2 No 60947-4-1 |
Uimp Rated Imp Wstd Voltage | 6 kV IEC 60947-6-2 |
Safe Separation Of Circuit | 400 V SELV between the control and auxiliary circuits IEC 60947-1 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 |
Fixing Mode | Plug-in front face) |
Width | 1.77 in (45 mm) |
Height | 2.60 in (66 mm) |
Depth | 2.36 in (60 mm) |
Product Weight | 0.30 lb(US) (0.135 kg) |
Compatibility Code | LUCA |
IP Degree Of Protection | IP20 front panel and wired terminals IEC 60947-1 IP20 other faces IEC 60947-1 IP40 front panel outside connection zone IEC 60947-1 |
Protective Treatment | TH IEC 60068 |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -40…185 °F (-40…85 °C) |
Operating Altitude | 6561.68 ft (2000 m) |
Fire Resistance | 1760 °F (960 °C) parts supporting live components IEC 60695-2-12 1202 °F (650 °C) IEC 60695-2-12 |
Shock Resistance | 10 gn power poles open IEC 60068-2-27 15 gn power poles closed IEC 60068-2-27 |
Vibration Resistance | 2 gn 5…300 Hz power poles open IEC 60068-2-6 4 gn 5…300 Hz power poles closed IEC 60068-2-6 |
Resist Electrostatic Dischrg | 8 kV 3 in open air IEC 61000-4-2 8 kV 4 on contact IEC 61000-4-2 |
Non-Dissipating Shock Wave | 1 kV serial mode IEC 60947-6-2 2 kV common mode IEC 60947-6-2 |
Resistance To Radiated Fields | 9.14 V/m (10 V/m) 3 IEC 61000-4-3 |
Resistance To Fast Transients | 2 kV 3 serial link IEC 61000-4-4 4 kV 4 all circuits except for serial link IEC 61000-4-4 |
Imm To Radioelectric Fields | 10 V IEC 61000-4-6 |
Immunity To Microbreaks | 3 ms |
Immunity To Voltage Dips | 70 % / 500 ms IEC 61000-4-11 |
Category | 22397 - TESYS U - CNTRL MOD(LUCA,LUCD) |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366