TeSys K – differential thermal overload relays – 12…16 A – class 10A
LR2K0322
TeSys K – differential thermal overload relays – 12…16 A – class 10A

TeSys LRK thermal overload relay, 16A/690V, thermal setting range 12-16A, tripping class 10A, for protection of 3-phase motors 7.5kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test slide switch for simulation of a tripping, reset/stop button, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1K16. Mounting on DIN rail, separated from the contactor, with use of a terminal block LA7K0064 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).

Add to Quote Catalogue
Specifications
Part Number LR2K0322
Country of Origin CZ
UPC 785901602514
UPC11 78590160251
EAN 3389110705898
Availability N
Lead Time 21
UNSPSC 39122330
ECCN EAR99
HTs Code 8536490075
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 2.56 inch
Height 2.28 inch
Width 1.77 inch
Weight 0.32 pound
Characteristics
Range TeSys
Product Name TeSys LRK
Product Or Component Type Differential thermal overload relay
Device Short Name LR2K
Relay Application Motor protection
Product Compatibility LP4K LP1K LC1K LC7K
Network Type AC DC
Thermal Overload Class Class 10A IEC 60947-4-1
Thermal Protection Adj Range 12…16 A
Ui Rated Insulation Voltage Power circuit 690 V BS 4941 Power circuit 690 V IEC 60947 Power circuit 750 V VDE 0110 group C Power circuit 600 V CSA C22.2 No 14
Network Frequency <= 400 Hz
Mounting Support Under contactor Plate, with specific accessories Rail, with specific accessories
Auxiliary Contact Composition 1 NO + 1 NC
Ith Cnvtl Free Air Therm Crrt 6 A signalling circuit
Ue Rated Operational Voltage <= 690 V power circuit 690 V AC AC-15 signalling circuit 250 V DC DC-13 signalling circuit
Associated Fuse Rating 6 A gG signalling circuit VDE 0660 6 A gG signalling circuit IEC 60947
Uimp Rated Imp Wstd Voltage 6 kV
Power Dissipation Per Pole 2 W
Phase Failure Sensitivity Yes IEC 60947-4-1
Local Signalling Trip indicator Yellow)
Control Type Red push-button trip test function Blue push-button stop and manual reset selector switch manual or automatic reset
Connections - Terminals screw clamp terminals 1 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 2 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…0.00 in² (0.34…1.5 mm²)flexible with cable end
Tightening Torque 11.51 lbf.in (1.3 N.m) screw clamp terminals Philips No 2 11.51 lbf.in (1.3 N.m) screw clamp terminals flat Ø 6 mm
Height 2.28 in (58 mm)
Width 1.77 in (45 mm)
Depth 2.56 in (65 mm)
Product Weight 0.32 lb(US) (0.145 kg)
Standards VDE 0660 IEC 60947 NF C 63-650 BS 4941
Product Certifications CSA UL
Protective Treatment TC IEC 60068 TC DIN 50016
IP Degree Of Protection IP2x IEC 60529
Ambient Air Temp For Op -4…131 °F (-20…55 °C) without derating IEC 60947 -22…140 °F (-30…60 °C) with derating IEC 60947
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Operating Altitude 6561.68 ft (2000 m) without derating
Fire Resistance 1562 °F (850 °C) IEC 60695-2-1
Flame Retardance V1 UL 94 Requirement 2 NF F 16-101 Requirement 2 NF F 16-102
Mechanical Robustness Shocks NO contact10 Gn for 11 ms IEC 60068-2-27 Shocks NC contact10 Gn for 11 ms IEC 60068-2-27 Vibrations NO contact2 Gn, 5...300 Hz IEC 60068-2-6 Vibrations NC contact2 Gn, 5...300 Hz IEC 60068-2-6
Category 22324 - CONTACTOR,K-LINE,OVERLOADS
Discount Schedule I12
GTIN 00785901602514
Nbr. Of Units In Pkg. 1
Country Of Origin CZ
Green Premium Status Green Premium product
REACh Free Of SVHC Yes
EU RoHs Directive Compliant
Mercury Free Yes
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Warranty 18 months
Documents