Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys Integral – reversing contactor breaker – 63 A AC-43 – 120 V AC coil
LD5LD030FC
TeSys Integral – reversing contactor breaker – 63 A AC-43 – 120 V AC coil
Specifications
Part Number LD5LD030FC
Country of Origin FR
UPC 785901872535
UPC11 78590187253
EAN 3389118099104
Availability S
Lead Time 17
UNSPSC 39121521
ECCN EAR99
HTs Code 8536504000
RoHS Compliant Yes
Discount Schedule I11
Return Indicator No
Depth 7.64 inch
Height 10.83 inch
Width 7.13 inch
Weight 16.76 pound
Characteristics
Range TeSys
Product Name TeSys Integral 63
Product Or Component Type Reversing contactor breaker
Device Short Name LD5LD
Utilisation Category AC-43
Poles Description 3P
Ue Rated Operational Voltage 690 V AC 50/60 Hz
Ie Rated Operational Current 63 A AC AC-43
Ith Cnvtl Free Air Therm Crrt 63 A 104 °F (40 °C)
Motor Power kW 15 kW 220...240 V AC 50/60 Hz 30 kW 400 V AC 50/60 Hz 33 kW 415 V AC 50/60 Hz 37 kW 500 V AC 50/60 Hz 55 kW 660 V AC 50/60 Hz 33 kW 440 V AC 50/60 Hz
[Uc] Control Circuit Voltage 120 V AC 60 Hz
Test Function Self test
Control Type Knob emergency stop Red front CNOMO
Irms Rated Making Capacity 756 A IEC 60947-4 946 A IEC 60947-4
Ipk Rated Peak Withstand Crrt 105 kA IEC 60947-2
Breaking Capacity Icu 10 kA 600...690 V 0.5) IEC 60947-2 Icu 30 kA 480...525 V 0.25) IEC 60947-6-2 Icu 50 kA <= 440 V 0.25) IEC 60947-2
Ics Rated Service Breaking Cap 10 kA 600...690 V IEC 60947-2 35 kA 480...525 V IEC 60947-2 50 kA <= 440 V IEC 60947-2
Maximum Breaking Time 4 ms
Thermal Stress Limit 300000 A².s
Uimp Rated Imp Wstd Voltage 8 kV IEC 60947-4
Ctrl Circuit Voltage Limits 0.25...0.7 Uc drop-out 131 °F (55 °C) 0.85...1.1 Uc operation 131 °F (55 °C)
Ui Rated Insulation Voltage 690 V IEC 60947-1
Inrush Power In VA 450 VA 60 Hz 68 °F (20 °C))
Hold-In Power Consumption Va 25 VA 68 °F (20 °C))
Heat Dissipation 5 W 32 A per pole, hot state power circuit 7 W 50 A per pole, hot state power circuit 9 W 63 A per pole, hot state power circuit 4.4 W 25 A per pole, hot state power circuit 5.8 W 40 A per pole, hot state power circuit 11 W at 60 Hz control circuit
Operating Time 12...35 ms AC closing 68 °F (20 °C) control circuit 7...20 ms AC opening 68 °F (20 °C) control circuit
Electrical Durability 1 Mcycles AC-3 3 kA 415 V - after 1 cycle O-CO-r-CO at Isc 0.9 Mcycles AC-3 10 kA 415 V - after 1 cycle O-CO-r-CO at Isc 0.6 Mcycles AC-3 25 kA 415 V - after 1 cycle O-CO-r-CO at Isc 0.5 Mcycles AC-3 35 kA 415 V - after 1 cycle O-CO-r-CO at Isc 0.2 Mcycles AC-3 50 kA 415 V - after 1 cycle O-CO-r-CO at Isc
Mechanical Durability 1.2 Mcycles
Connections - Terminals Power circuit screw clamp terminals 1 0.01…0.08 in² (6…50 mm²) flexible - without cable end Power circuit screw clamp terminals 2 0.01…0.04 in² (6…25 mm²) flexible - without cable end Power circuit screw clamp terminals 1 0.01…0.04 in² (6…25 mm²) flexible - with cable end Power circuit screw clamp terminals 2 0.01…0.04 in² (6…25 mm²) flexible - with cable end Power circuit screw clamp terminals 1 0.01…0.08 in² (6…50 mm²) solid
Tightening Torque Power circuit 53.10 lbf.in (6 N.m) screw clamp terminals
Width 7.13 in (181 mm)
Height 10.83 in (275 mm)
Depth 7.64 in (194 mm)
Product Weight 16.76 lb(US) (7.6 kg)
Standards IEC 60158-1 NF C 63-130 NF C 63-120 NF C 63-650 IEC 60204-1 IEC 60947-2 NF C 63-110 BS 5424 NF C 79-100 VDE 0113 VDE 0660 IEC 60947-1 IEC 60364 VDE 471 VDE 0170 NEN BS 4752 VDE 0110 VDE 0100 BS 4941 VDE 0171 IEC 60204-2 NF C 20-040 NBN IEC 60947-4
Product Certifications LROS (Lloyds register of shipping) OVE GL UL BV DNV ASEFA NKK USSR DEMKO SCC CSA ASTA NEMKO RINA ASE SETI
Protective Treatment TH
Ambient Air Temp For Op -4…140 °F (-20…60 °C)
Ambient Air Temp For Storage -40…176 °F (-40…80 °C)
Mechanical Robustness Vibrations de-energised3 Gn, 1...300 Hz Vibrations energised3 Gn, 1...300 Hz Shocks de-energised8 Gn for 11 ms Shocks energised8 Gn for 11 ms
IP Degree Of Protection IP20 B IEC 60144 IP20 B IEC 60529
Operating Altitude 9842.52 ft (3000 m) without derating
Category 22382 - STRS,INTEGRAL 32&63,OPEN
Discount Schedule I11
GTIN 00785901872535
Nbr. Of Units In Pkg. 1
Country Of Origin FR
REACh Free Of SVHC Yes
EU RoHs Directive Compliant
Mercury Free Yes
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews