GV3P32 is a TeSys GV motor circuit breaker from Schneider Electric. It ensures thermal-magnetic protection for motors 15kW@400V and high breaking capacity Icu 100kA. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3 415V. GV3P32 is a TeSys GV motor circuit breaker from Schneider Electric designed for motor applications 15kW@400V. It fulfills a thermal-magnetic protection with a thermal setting range 23-32A, magnetic tripping at 14xIn and high breaking capacity Icu 100kA@400V. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3 415V. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Complete motor protection in a single device , short-circuit, overload, disconnection. Associated with a TeSys contactor, it ensures a complete type 1 or type 2 Motor Starter solution. Compact, 55mm wide, for DIN-rail and panel mounting. Manual control with rotary knob for Start / Stop, padlockable. Possible mounting of auxiliary contacts front or side mounted (GVAE, GVAN, GVAD) for status and tripping signaling. For large industrial or building LV distribution networks thanks to a high 100kA breaking capacity. Power connections with EverLink BTR screw connectors providing constant tightening pressure. Can be associated with undervoltage or shunt tripping units (GVAU, GVAS) and power distribution busbars (GV3G).
Add to Quote CataloguePart Number | GV3P32 |
---|---|
Country of Origin | FR |
UPC | 785901492337 |
UPC11 | 78590149233 |
EAN | 3389119405386 |
Availability | S |
Lead Time | 3 |
UNSPSC | 39121521 |
ECCN | EAR99 |
HTs Code | 8536200020 |
Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | I11 |
Return Indicator | Yes |
Depth | 5.35 inch |
Height | 5.20 inch |
Width | 2.17 inch |
Weight | 2.12 pound |
Range | TeSys |
---|---|
Product Name | TeSys GV3 |
Device Short Name | GV3P |
Device Application | Motor |
Trip Unit Technology | Thermal-magnetic |
Poles Description | 3P |
Network Type | AC |
Utilisation Category | AC-3 IEC 60947-4-1 Category A IEC 60947-2 |
Network Frequency | 50/60 Hz IEC 60947-4-1 |
Fixing Mode | 35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws) |
Operating Position | Any position |
Motor Power kW | 15 kW 400/415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 690 V AC 50/60 Hz |
Breaking Capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2 12 kA Icu 500 V AC 50/60 Hz IEC 60947-2 |
Ics Rated Ser Sc Brking Cap | 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 50 % 500 V AC 50/60 Hz IEC 60947-2 50 % 690 V AC 50/60 Hz IEC 60947-2 |
Control Type | Rotary knob |
In Rated Current | 32 A |
Thermal Protection Adjustment Range | 23…32 A |
Magnetic Tripping Current | 448 A |
Ue Rated Operational Voltage | 690 V AC 50/60 Hz IEC 60947-2 |
Ui Rated Insulation Voltage | 690 V AC 50/60 Hz IEC 60947-2 |
Ith Cnvtl Free Air Therm Crrt | 32 A IEC 60947-4-1 |
Uimp Rated Imp Wstd Voltage | 6 kV IEC 60947-2 |
Power Dissipation Per Pole | 8 W |
Mechanical Durability | 50000 cycles |
Electrical Durability | 50000 cycles AC-3 440 V In |
Operating Rate | 25 cyc/h |
Rated Duty | Continuous IEC 60947-4-1 |
Connections - Terminals | EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²) solid EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²) flexible without cable end EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²) flexible with cable end |
Tightening Torque | 44.25 lbf.in (5 N.m) EverLink BTR screw connectors 0.04 in² (25 mm²) 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.05 in² (35 mm²) |
Suitability For ISOlation | Yes IEC 60947-1 |
Phase Failure Sensitivity | Yes IEC 60947-4-1 |
Height | 5.20 in (132 mm) |
Width | 2.17 in (55 mm) |
Depth | 5.35 in (136 mm) |
Product Weight | 2.12 lb(US) (0.96 kg) |
Standards | EN/IEC 60947-2 EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1 UL 60947-4-1 |
Product Certifications | IECEE CB Scheme UL CSA CCC EAC ATEX BV LROS (Lloyds register of shipping) DNV-GL ABS |
Protective Treatment | TH |
IP Degree Of Protection | IP20 IEC 60529 |
IK Degree Of Protection | IK09 |
Ambient Air Temp For Op | -4…140 °F (-20…60 °C) |
Ambient Air Temp For Storage | -40…176 °F (-40…80 °C) |
Fire Resistance | 1760 °F (960 °C) IEC 60695-2-1 |
Operating Altitude | 9842.52 ft (3000 m) |
Category | 22366 - MAN STR PROTECTORS-GV1/GV3 |
Discount Schedule | I11 |
GTIN | 00785901492337 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | FR |
Green Premium Status | Green Premium product |