Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys F contactor – 3P(3 NO)-AC-3
LC1F630
TeSys F contactor – 3P(3 NO)-AC-3

TeSys F contactor, 3 poles (3NO), 630A/1000V AC-3, for motor applications up to 250kW@400V. Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs. For high operating rates until 1200 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LC1F630
Country of Origin CZ
UPC 785901098331
UPC11 78590109833
EAN 3389110122183
Availability S
Lead Time 3
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator Yes
Depth 10.04 inch
Height 11.97 inch
Width 12.17 inch
Weight 41.01 pound
Characteristics
Range TeSys
Product Name TeSys F
Product Or Component Type Contactor
Device Short Name LC1F
Contactor Application Resistive load Motor control
Utilisation Category AC-4 AC-1 AC-3
Poles Description 3P
Power Pole Contact Composition 3 NO
Ue Rated Operational Voltage <= 1000 V AC 50/60 Hz <= 460 V DC
Ie Rated Operational Current 1000 A 104 °F (40 °C)) <= 440 V AC AC-1 630 A 131 °F (55 °C)) <= 440 V AC AC-3
Motor Power kW 335 kW 380...400 V AC 50/60 Hz AC-3) 375 kW 415 V AC 50/60 Hz AC-3) 400 kW 440 V AC 50/60 Hz AC-3) 400 kW 500 V AC 50/60 Hz AC-3) 450 kW 1000 V AC 50/60 Hz AC-3) 200 kW 220...240 V AC 50/60 Hz AC-3) 450 kW 660...690 V AC 50/60 Hz AC-3) 100 kW 400 V AC 50/60 Hz AC-4)
Uc Control Circuit Voltage 48...1000 V AC 40...400 Hz with LX1/LX9 coil 48...440 V DC with LX4 coil
Uimp Rated Imp Wstd Voltage 8 kV
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 1000 A 104 °F (40 °C) 1250 A
Irms Rated Making Capacity 6300 A AC IEC 60947-4-1
Rated Breaking Capacity 5040 A IEC 60947-4-1
Icw Rated Short-Time Wstd Crrt 5050 A 104 °F (40 °C) - 10 s 4400 A 104 °F (40 °C) - 30 s 3400 A 104 °F (40 °C) - 1 min 2200 A 104 °F (40 °C) - 3 min 1600 A 104 °F (40 °C) - 10 min
Associated Fuse Rating 630 A aM <= 440 V 1000 A gG <= 440 V
Average Impedance 0.12 mOhm - Ith 1000 A 50 Hz
Ui Rated Insulation Voltage 1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power Dissipation Per Pole 120 W AC-1 48 W AC-3
Ctrl Circuit Voltage Limits Operational 0.85...1.1 Uc AC 40...400 Hz Drop-out 0.25...0.5 Uc AC 40...400 Hz Operational 0.85...1.1 Uc DC Drop-out 0.2...0.35 Uc DC
Heat Dissipation 20 W
Operating Time 40...80 ms closing with LX1/LX9 coil 100...200 ms opening with LX1/LX9 coil 60...70 ms closing with LX4 coil 40...50 ms opening with LX4 coil
Mounting Support Plate
Standards EN 60947-4-1 IEC 60947-4-1 IEC 60947-1 JIS C8201-4-1 EN 60947-1
Product Certifications ABS UL RINA DNV CSA CB LROS (Lloyds register of shipping) BV RMRoS
Connections - Terminals Power circuit bar 2 60 x 5 mm Power circuit bolted connection Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)solid without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)
Tightening Torque Power circuit 513.34 lbf.in (58 N.m) Control circuit 10.62 lbf.in (1.2 N.m)
Mechanical Durability 5 Mcycles
Inrush Power In VA 1500…1730 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 1420…1920 VA (at 68 °F (20 °C))with LX4 coil
Hold-In Power Consumption Va 20…25 VA 6.5…12.5 VA
Operating Rate 1200 cyc/h 131 °F (55 °C)
Compatibility Code LC1F
IP Degree Of Protection IP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Protective Treatment TH
Ambient Air Temp For Op 23…131 °F (-5…55 °C)
Ambient Air Temp For Storage -76…176 °F (-60…80 °C)
Ambient Air Temp Around Device -40…158 °F (-40…70 °C)
Operating Altitude 9842.52 ft (3000 m) without derating
Mechanical Robustness Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open6 Gn for 1/2 sine wave (11 ms) Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height 11.97 in (304 mm)
Width 12.17 in (309 mm)
Depth 10.04 in (255 mm)
Product Weight 41.01 lb(US) (18.6 kg)
Category 22336 - CTR,F-LINE,AC,OPEN,NONREV
Discount Schedule I12
GTIN 00785901098331
Nbr. Of Units In Pkg. 1
Documents