Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys F contactor – 3P (3 NO) – AC-3 –
LC1F400F7
TeSys F contactor – 3P (3 NO) – AC-3 –

TeSys F contactor, 3 poles (3NO), 400A/1000V AC-3, for motor applications up to 200kW@400V. It provides a low sealed consumption 110V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LC1F400F7
Country of Origin CZ
UPC 785901079866
UPC11 78590107986
EAN 3389110226942
Availability S
Lead Time 37
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator Yes
Depth 8.62 inch
Height 8.11 inch
Width 8.39 inch
Weight 20.06 pound
Characteristics
Range TeSys
Product Name TeSys F
Product Or Component Type Contactor
Device Short Name LC1F
Contactor Application Resistive load Motor control
Utilisation Category AC-1 AC-4 AC-3
Poles Description 3P
Power Pole Contact Composition 3 NO
Ue Rated Operational Voltage <= 1000 V AC 50/60 Hz <= 460 V DC
Ie Rated Operational Current 500 A 104 °F (40 °C)) <= 440 V AC AC-1 400 A 131 °F (55 °C)) <= 440 V AC AC-3
Motor Power kW 75 kW 400 V AC 50/60 Hz AC-4) 200 kW 380...400 V AC 50/60 Hz AC-3) 220 kW 415 V AC 50/60 Hz AC-3) 250 kW 440 V AC 50/60 Hz AC-3) 257 kW 500 V AC 50/60 Hz AC-3) 280 kW 660...690 V AC 50/60 Hz AC-3) 185 kW 1000 V AC 50/60 Hz AC-3) 110 kW 220...230 V AC 50/60 Hz AC-3)
Uc Control Circuit Voltage 110 V AC 40...400 Hz
Uimp Rated Imp Wstd Voltage 8 kV
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 500 A 104 °F (40 °C)
Rated Breaking Capacity 3200 A IEC 60947-4-1
Icw Rated Short-Time Wstd Crrt 3600 A 104 °F (40 °C) - 10 s 2400 A 104 °F (40 °C) - 30 s 1700 A 104 °F (40 °C) - 1 min 1200 A 104 °F (40 °C) - 3 min 1000 A 104 °F (40 °C) - 10 min
Associated Fuse Rating 400 A aM <= 440 V 500 A gG <= 440 V
Average Impedance 0.26 mOhm - Ith 500 A 50 Hz
Ui Rated Insulation Voltage 1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power Dissipation Per Pole 65 W AC-1 42 W AC-3
Mounting Support Plate
Standards IEC 60947-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-4-1 EN 60947-1
Product Certifications BV UL CB ABS RINA CSA RMRoS DNV LROS (Lloyds register of shipping)
Connections - Terminals Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end Power circuit bar 2 30 x 5 mm Power circuit lugs-ring terminals 2 0.23 in² (150 mm²) Power circuit bolted connection
Tightening Torque Control circuit 10.62 lbf.in (1.2 N.m) Power circuit 309.78 lbf.in (35 N.m)
Ctrl Circuit Voltage Limits Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C))
Inrush Power In VA 1075 VA 40...400 Hz 0.9 68 °F (20 °C))
Hold-In Power Consumption Va 15 VA 40...400 Hz 0.9 68 °F (20 °C))
Heat Dissipation 14 W
Operating Time 40...65 ms closing 100...170 ms opening
Mechanical Durability 10 Mcycles
Operating Rate 2400 cyc/h 131 °F (55 °C)
Compatibility Code LC1F
Motor Power Range 110…220 kW 480…500 V 3 phase 110…220 kW 380…440 V 3 phase 110…220 kW 200…240 V 3 phase 250…500 kW 480…500 V 3 phase
Motor Starter Type Direct on-line contactor
Contactor Coil Voltage 110 V AC standard
IP Degree Of Protection IP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Protective Treatment TH
Ambient Air Temp For Op 23…131 °F (-5…55 °C)
Ambient Air Temp For Storage -76…176 °F (-60…80 °C)
Ambient Air Temp Around Device -40…158 °F (-40…70 °C)
Height 8.11 in (206 mm)
Width 8.39 in (213 mm)
Depth 8.62 in (219 mm)
Product Weight 20.06 lb(US) (9.1 kg)
Category 22336 - CTR,F-LINE,AC,OPEN,NONREV
Discount Schedule I12
GTIN 00785901079866
Nbr. Of Units In Pkg. 1
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews