LC2D65ABD is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 65A AC-3 30kW@400V, it includes a 24V DC coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D65ABD is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 30kW@400V. It includes a 24V DC coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 119mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 24V DC coil for easy integration to all control systems. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 1.6 million cycles at 65A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Power connections by EverLink BTR screw terminals providing constant tightening pressure.
Add to Quote CataloguePart Number | LC2D65ABD |
---|---|
Country of Origin | FR |
UPC | 785901830436 |
UPC11 | 78590183043 |
EAN | 3389118339163 |
Availability | N |
Lead Time | 48 |
UNSPSC | 39121529 |
ECCN | EAR99 |
HTs Code | 8536490065 |
Prop 65 | This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | I12 |
Return Indicator | Yes |
Depth | 4.72 inch |
Height | 4.80 inch |
Width | 4.69 inch |
Weight | 4.50 pound |
Range | TeSys |
---|---|
Product Name | TeSys D |
Product Or Component Type | Reversing contactor |
Device Short Name | LC2D |
Contactor Application | Resistive load Motor control |
Utilisation Category | AC-3 AC-1 |
Device Presentation | Preassembled with reversing power busbar |
Poles Description | 3P |
Power Pole Contact Composition | 3 NO |
Ue Rated Operational Voltage | Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC |
Ie Rated Operational Current | 80 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit 65 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit |
Motor Power kW | 18.5 kW 220...230 V AC 50 Hz 30 kW 380...400 V AC 50 Hz 37 kW 415...440 V AC 50 Hz 37 kW 500 V AC 50 Hz 37 kW 660...690 V AC 50 Hz |
Motor Power Hp (Ul / Csa) | 40 hp 460/480 V AC 60 Hz 3 phase 5 hp 115 V AC 60 Hz 1 phase 10 hp 230/240 V AC 60 Hz 1 phase 20 hp 200/208 V AC 60 Hz 3 phase 20 hp 230/240 V AC 60 Hz 3 phase 50 hp 575/600 V AC 60 Hz 3 phase |
Control Circuit Type | DC standard |
Uc Control Circuit Voltage | 24 V DC |
Auxiliary Contact Composition | 1 NO + 1 NC |
Uimp Rated Imp Wstd Voltage | 6 kV IEC 60947 |
Overvoltage Category | III |
Ith Cnvtl Free Air Therm Crrt | 10 A 140 °F (60 °C) signalling circuit 80 A 140 °F (60 °C) power circuit |
Irms Rated Making Capacity | 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 1000 A 440 V power circuit IEC 60947 |
Rated Breaking Capacity | 1000 A 440 V power circuit IEC 60947 |
Icw Rated Short-Time Wstd Crrt | 520 A 104 °F (40 °C) - 10 s power circuit 900 A 104 °F (40 °C) - 1 s power circuit 110 A 104 °F (40 °C) - 10 min power circuit 260 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit |
Associated Fuse Rating | 10 A gG signalling circuit IEC 60947-5-1 125 A gG <= 690 V type 1 power circuit 125 A gG <= 690 V type 2 power circuit |
Average Impedance | 1.5 mOhm - Ith 80 A 50 Hz power circuit |
Ui Rated Insulation Voltage | Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL |
Electrical Durability | 1.45 Mcycles 65 A AC-3 <= 440 V 1.4 Mcycles 80 A AC-1 <= 440 V |
Power Dissipation Per Pole | 9.6 W AC-1 6.3 W AC-3 |
Front Cover | With |
Interlocking Type | Mechanical |
Mounting Support | Rail Plate |
Standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
Product Certifications | UL CCC GOST CSA |
Connections - Terminals | Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid Power circuit EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²)flexible without cable end Power circuit EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²)flexible without cable end Power circuit EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²)flexible with cable end Power circuit EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²)flexible with cable end Power circuit EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²)solid Power circuit EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²)solid |
Tightening Torque | Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagonal 0.16 in (4 mm) Power circuit 44.25 lbf.in (5 N.m) EverLink BTR screw connectors 0.00…0.04 in² (1…25 mm²) hexagonal 0.16 in (4 mm) |
Operating Time | 16...24 ms opening 42.5...57.5 ms closing |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Mechanical Durability | 10 Mcycles |
Operating Rate | 3600 cyc/h 140 °F (60 °C) |
Coil Technology | Built-in bidirectional peak limiting diode suppressor |
Ctrl Circuit Voltage Limits | 0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC 0.75...1.25 Uc -40…140 °F (-40…60 °C) operational DC 1...1.25 Uc 140…158 °F (60…70 °C) operational DC |
Time Constant | 34 ms |
Inrush Power In W | 19 W 68 °F (20 °C)) |
Hold-In Power Consumption W | 7.4 W 68 °F (20 °C) |
Auxiliary Contacts Type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1 |
Signalling Circuit Frequency | 25...400 Hz |
Minimum Switching Current | 5 mA signalling circuit |
Minimum Switching Voltage | 17 V signalling circuit |
Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
Insulation Resistance | > 10 MOhm signalling circuit |
Contact Compatibility | M4 |