Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys D reversing contactor – 3P –
LC2D32KUE
TeSys D reversing contactor – 3P –

LC2D32KUE is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 32A AC-3 15kW@400V, it includes a 100-250V AC/DC low consumption electronic coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D32KUE is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 15kW@400V. It includes a 100-250V AC/DC low consumption electronic coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with an electronic coil, wide band voltage 100-250V, AC/DC compatible, low consumption. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 2 million cycles at 32A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.

Add to Quote Catalogue
Specifications
Part Number LC2D32KUE
UPC 606480988042
UPC11 60648098804
EAN 3606480988042
Availability N
Lead Time 20
UNSPSC 39121529
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 3.62 inch
Height 3.35 inch
Width 3.54 inch
Weight 2.03 pound
Characteristics
Range TeSys
Product Name TeSys D Green
Product Or Component Type Reversing contactor
Device Short Name LC2D
Contactor Application Resistive load Motor control
Utilisation Category AC-1 AC-3
Device Presentation Preassembled with reversing power busbar
Poles Description 3P
Power Pole Contact Composition 3 NO
Ue Rated Operational Voltage Power circuit <= 690 V AC 25...400 Hz
Ie Rated Operational Current 32 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 50 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
Motor Power kW 7.5 kW 220...230 V AC 50 Hz 15 kW 380...400 V AC 50 Hz 15 kW 415 V AC 50 Hz 15 kW 440 V AC 50 Hz 18.5 kW 500 V AC 50 Hz 18.5 kW 660...690 V AC 50 Hz
Motor Power Hp (Ul / Csa) 2 hp 115 V AC 60 Hz 1 phase 5 hp 230/240 V AC 60 Hz 1 phase 10 hp 200/208 V AC 60 Hz 3 phase 10 hp 230/240 V AC 60 Hz 3 phase 20 hp 460/480 V AC 60 Hz 3 phase 25 hp 575/600 V AC 60 Hz 3 phase
Control Circuit Type AC 50/60 Hz AC/DC electronic DC AC/DC electronic
Uc Control Circuit Voltage 100...250 V AC 50/60 Hz 100...250 V DC
Auxiliary Contact Composition 1 NO + 1 NC
Uimp Rated Imp Wstd Voltage 6 kV IEC 60947
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 10 A 140 °F (60 °C) signalling circuit 50 A 140 °F (60 °C) power circuit
Irms Rated Making Capacity 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 550 A 440 V power circuit IEC 60947
Rated Breaking Capacity 550 A 440 V power circuit IEC 60947
Icw Rated Short-Time Wstd Crrt 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit 260 A 104 °F (40 °C) - 10 s power circuit 430 A 104 °F (40 °C) - 1 s power circuit 60 A 104 °F (40 °C) - 10 min power circuit 138 A 104 °F (40 °C) - 1 min power circuit
Associated Fuse Rating 10 A gG signalling circuit IEC 60947-5-1 63 A gG <= 690 V type 1 power circuit 63 A gG <= 690 V type 2 power circuit
Average Impedance 2 mOhm - Ith 50 A 50 Hz power circuit
Ui Rated Insulation Voltage Power circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-1
Electrical Durability 2.1 Mcycles 29 A AC-3 <= 440 V 0.9 Mcycles 50 A AC-1 <= 440 V
Power Dissipation Per Pole 2 W AC-3 5 W AC-1
Front Cover With
Interlocking Type Mechanical
Mounting Support Rail Plate
Standards EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
Product Certifications CCC CSA EAC UL KC DNV-GL LROS (Lloyds register of shipping)
Connections - Terminals Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid Power circuit screw clamp terminals 1 0.00…0.02 in² (2.5…10 mm²)flexible without cable end Power circuit screw clamp terminals 2 0.00…0.02 in² (2.5…10 mm²)flexible without cable end Power circuit screw clamp terminals 1 0.00…0.02 in² (1…10 mm²)flexible with cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²)flexible with cable end Power circuit screw clamp terminals 1 0.00…0.02 in² (1.5…10 mm²)solid Power circuit screw clamp terminals 2 0.00…0.02 in² (2.5…10 mm²)solid
Tightening Torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 22.13 lbf.in (2.5 N.m) screw clamp terminals flat Ø 6 mm Power circuit 22.13 lbf.in (2.5 N.m) screw clamp terminals Philips No 2
Operating Time 45...55 ms closing 20...90 ms opening
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability 15 Mcycles
Operating Rate 3600 cyc/h 140 °F (60 °C)
Coil Technology Built-in bidirectional peak limiting
Ctrl Circuit Voltage Limits <= 0.1 Uc -40…158 °F (-40…70 °C) drop-out AC/DC 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC/DC 1...1.1 Uc 140…158 °F (60…70 °C) operational AC/DC
Inrush Power In VA 25 VA 50/60 Hz 68 °F (20 °C))
Inrush Power In W 18 W 68 °F (20 °C)
Hold-In Power Consumption Va 1.6 VA 68 °F (20 °C)) 50/60 Hz
Hold-In Power Consumption W 1.1 W 68 °F (20 °C)
Heat Dissipation 1.1 W 50/60 Hz
Auxiliary Contacts Type Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
Signalling Circuit Frequency 25...400 Hz
Minimum Switching Current 5 mA signalling circuit
Minimum Switching Voltage 17 V signalling circuit
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact