Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
TeSys D contactor S207 – 3P (3NO) AC-3 9A
LC1D096SLS207
TeSys D contactor S207 – 3P (3NO) AC-3 9A

TeSys D contactor, 3 poles (3NO), for motor control in railway applications up to 9A/690V AC-3 (4kW@400V). It provides a low consumption 72V DC coil with transient suppressor module, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by ring-lugs screw terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability to demanding applications. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, CCC, EAC) and compliant with the railway European standard EN 45545 R22HL3, Green Premium product (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LC1D096SLS207
Country of Origin FR
UPC 389118234222
UPC11 38911823422
EAN 3389118234222
Availability N
Lead Time 20
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490065
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 3.74 inch
Height 3.03 inch
Width 1.77 inch
Weight 0.71 pound
Characteristics
Range TeSys
Product Name TeSys D
Product Or Component Type Contactor
Device Short Name LC1D
Contactor Application Resistive load Motor control
Utilisation Category AC-3 AC-1
Poles Description 3P
Power Pole Contact Composition 3 NO
Ue Rated Operational Voltage Power circuit <= 690 V AC 25...400 Hz
Ie Rated Operational Current 9 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 25 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
Motor Power kW 2.2 kW 220/230 V AC 50 Hz AC-3) 4 kW 380/400 V AC 50 Hz AC-3) 4 kW 415 V AC 50 Hz AC-3) 4 kW 440 V AC 50 Hz AC-3) 5.5 kW 500 V AC 50 Hz AC-3) 5.5 kW 660/690 V AC 50 Hz AC-3)
Uc Control Circuit Voltage 72 V DC
Coil Type Low consumption
Auxiliary Contact Composition 1 NO + 1 NC
Uimp Rated Imp Wstd Voltage 6 kV IEC 60947
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 10 A 140 °F (60 °C) signalling circuit 25 A 140 °F (60 °C) power circuit
Irms Rated Making Capacity 250 A 440 V power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1
Rated Breaking Capacity 250 A 440 V power circuit IEC 60947
Icw Rated Short-Time Wstd Crrt 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit 105 A 104 °F (40 °C) - 10 s power circuit 210 A 104 °F (40 °C) - 1 s power circuit 30 A 104 °F (40 °C) - 10 min power circuit 61 A 104 °F (40 °C) - 1 min power circuit
Associated Fuse Rating 10 A gG signalling circuit IEC 60947-5-1 25 A gG <= 690 V type 1 power circuit 20 A gG <= 690 V type 2 power circuit
Average Impedance 2.5 mOhm - Ith 25 A 50 Hz power circuit
Ui Rated Insulation Voltage Power circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-1
Electrical Durability 0.6 Mcycles 25 A AC-1 <= 440 V 2 Mcycles 9 A AC-3 <= 440 V
Power Dissipation Per Pole 1.56 W AC-1 0.2 W AC-3
Front Cover With
Mounting Support Rail Plate
Standards EN/IEC 60947-4-1 EN/IEC 60947-5-1 EN 45545 R22 HL3 EN 45545 R26 HL3 DIN 5510-2
Product Certifications IEC CCC EAC UA TR
Connections - Terminals Control circuit lugs-ring terminals 0.31 in (8 mm)) Power circuit lugs-ring terminals 0.37 in (9.5 mm))
Tightening Torque Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5
Operating Time 55...75 ms closing 16...32 ms opening
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability 30 Mcycles
Operating Rate 3600 cyc/h 140 °F (60 °C)
Coil Technology With integral suppression device
Ctrl Circuit Voltage Limits 0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC 0.7...1.25 Uc -40…158 °F (-40…70 °C) operational DC
Time Constant 37 ms
Inrush Power In W 4 W 68 °F (20 °C)
Hold-In Power Consumption W 4 W 68 °F (20 °C)
Auxiliary Contacts Type Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
Signalling Circuit Frequency 25...400 Hz
Minimum Switching Current 5 mA signalling circuit
Minimum Switching Voltage 17 V signalling circuit
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
Insulation Resistance > 10 MOhm signalling circuit
Contact Compatibility M5
Compatibility Code LC1D
IP Degree Of Protection IP20 front face IEC 60529
Protective Treatment TH IEC 60068-2-30
Documents