Specifications
Part Number LP1D65008JD
Country of Origin CZ
UPC 389110202717
UPC11 38911020271
EAN 3389110202717
Availability N
Lead Time 18
ECCN EAR99
HTs Code 8536490075
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 7.17 inch
Height 5.00 inch
Width 3.35 inch
Weight 4.89 pound
Characteristics
Range TeSys
Product Name TeSys D
Product Or Component Type Contactor
Device Short Name LP1D
Contactor Application Resistive load
Utilisation Category AC-1
Poles Description 4P
Power Pole Contact Composition 2 NO + 2 NC
Ue Rated Operational Voltage Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
Ie Rated Operational Current 80 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
Uc Control Circuit Voltage 12 V DC
Coil Type DC standard
Uimp Rated Imp Wstd Voltage 6 kV IEC 60947
Overvoltage Category III
Ith Cnvtl Free Air Therm Crrt 80 A 140 °F (60 °C) power circuit
Irms Rated Making Capacity 1000 A 440 V power circuit IEC 60947
Rated Breaking Capacity 1000 A 440 V power circuit IEC 60947
Icw Rated Short-Time Wstd Crrt 110 A 104 °F (40 °C) - 10 min power circuit 260 A 104 °F (40 °C) - 1 min power circuit 520 A 104 °F (40 °C) - 10 s power circuit 900 A 104 °F (40 °C) - 1 s power circuit
Associated Fuse Rating 125 A gG <= 690 V type 1 power circuit 125 A gG <= 690 V type 2 power circuit
Average Impedance 1.5 mOhm - Ith 80 A 50 Hz power circuit
Ui Rated Insulation Voltage Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL
Electrical Durability 1.4 Mcycles 80 A AC-1 <= 440 V
Power Dissipation Per Pole 9.6 W AC-1
Front Cover Without
Mounting Support Plate Rail
Standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
Product Certifications BV CCC CSA DNV EAC GL LROS (Lloyds register of shipping) UL
Connections - Terminals Power circuit screw clamp terminals 1 0.00…0.05 in² (1…35 mm²)flexible without cable end Power circuit screw clamp terminals 2 0.00…0.04 in² (1…25 mm²)flexible without cable end Power circuit screw clamp terminals 1 0.00…0.05 in² (1…35 mm²)flexible with cable end Power circuit screw clamp terminals 2 0.00…0.04 in² (1…25 mm²)flexible with cable end Power circuit screw clamp terminals 1 0.00…0.05 in² (1…35 mm²)solid Power circuit screw clamp terminals 2 0.00…0.04 in² (1…25 mm²)solid Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid
Tightening Torque Power circuit 70.81 lbf.in (8 N.m) screw clamp terminals 0.04…0.05 in² (25…35 mm²) hexagonal 0.16 in (4 mm) Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 44.25 lbf.in (5 N.m) screw clamp terminals 0.00…0.04 in² (1…25 mm²) hexagonal 0.16 in (4 mm)
Operating Time 4...19 ms opening 12...26 ms closing
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability 6 Mcycles
Operating Rate 3600 cyc/h 140 °F (60 °C)
Coil Technology Built-in bidirectional peak limiting diode suppressor
Ctrl Circuit Voltage Limits 0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC 0.85...1.1 Uc -40…131 °F (-40…55 °C) operational DC 1...1.1 Uc 131…158 °F (55…70 °C) operational DC
Time Constant 75 ms
Inrush Power In W 22 W 68 °F (20 °C)
Hold-In Power Consumption W 22 W 68 °F (20 °C)
Contact Compatibility M3
Compatibility Code LP1D
IP Degree Of Protection IP20 front face IEC 60529
Protective Treatment TH IEC 60068-2-30
Pollution Degree 3
Ambient Air Temp For Op -40…140 °F (-40…60 °C) 140…158 °F (60…70 °C) with derating
Ambient Air Temp For Storage -76…176 °F (-60…80 °C)
Operating Altitude 0...9842.52 ft (0...3000 m)
Fire Resistance 1562 °F (850 °C) IEC 60695-2-1
Flame Retardance V1 UL 94
Mechanical Robustness Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open10 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms
Height 5.00 in (127 mm)