Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Safety controller XPS-MC – 24 V DC – 16 input – 30 LEDs signalling
XPSMC16Z
Safety controller XPS-MC – 24 V DC – 16 input – 30 LEDs signalling

This product is part of the Preventa XPS MP, XPS MC, XPS MCM range, an offer of safety controllers. This safety controller provides 16 inputs and 30 LEDs for signalling. It is a safety controller with a power consumption of 12W, control circuit voltage of 28.8V and a rated supply voltage of 24V DC. Supported communication port protocol is Modbus with RJ45 port. Conventional free air thermal current 16A for relay output and 6.5A for static output circuit. It is an IP20 rated product. Its dimensions are 74mm (Width) x 153mm (Depth) x 151.5mm (Height). It weighs 0.82kg. It is designed to provide a solution for safety applications requiring conformity to Performance Level PL e/Category 4 EN/ISO 13849-1 and SIL3 EN/IEC 61508. This product is certified by UL, CSA and TUV. It meets EN 574/ISO 13851, EN 1760-1/ISO 13856-1, EN/IEC 61496-1, EN/IEC 60204-1, EN/IEC 60947-5-1, EN 954-1/EN/ISO 13849-1 and IEC 61508 standards. Simple, it features redundancy principle micro-processor based technology to provide advanced functions, flexibility regarding the choice of safety function and more precise diagnostics are just some of its advantages. Safety controller XPS MC is configured with a simple software environment where functions are mapped to the various controller outputs according to the application requirements.

Brand: Telemecanique

Add to Quote Catalogue
Specifications
Part Number XPSMC16Z
Country of Origin FR
UPC 785901974932
UPC11 78590197493
EAN 3389119010245
Availability N
Lead Time 33
UNSPSC 32151802
HTs Code 8537109160
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule SAF2
Return Indicator Yes
Depth 6.02 inch
Height 5.96 inch
Width 2.91 inch
Weight 1.81 pound
Characteristics
Range Of Product Preventa Safety automation
Product Or Component Type Configurable safety controller
Safety Module Name XPSMC
Safety Use Category Category 4 maximum EN 954-1/EN/ISO 13849-1 PLE maximum EN/ISO 13849-1 SIL 3 maximum IEC 61508
Type Of Start Configurable
Standards EN 574/ISO 13851 EN 1760-1/ISO 13856-1 EN/IEC 61496-1 EN/IEC 60204-1 IEC 61508 EN/IEC 60947-5-1 EN 954-1/EN/ISO 13849-1
Product Certifications TÜV UL CSA
Us Rated Supply Voltage 24 V DC - 20...20 %
Number Of Inputs 16
Communication Port Protocol Modbus 1 RJ45, serial link 1200 bps, 2400 bps, 4800 bps, 9600 bps or 19200 bps
Safety Level Can reach PL e/category 4 EN 954-1/EN/ISO 13849-1 Can reach SIL 3 IEC 61508
Function Of Module Dynamic monitoring of hydraulic valves on linear presses Eccentric press Emergency stop monitoring, with or without time delay, 1 or 2-channel wiring Enabling switch monitoring, 2 or 3 contacts Foot switch monitoring Guard monitoring for injection presses and blowing machines Guard monitoring with 1 or 2 limit switches Hydraulic press Magnetic switch monitoring Monitoring safety stop at top dead centre on eccentric press Muting function of light curtains Position selector Safety mat monitoring Safety time delays Shaft/chain breaking monitor Zero speed detection Light curtain monitoring category 4 EN/IEC 61496 Two-hand control category 3 EN 574/ISO 13851
Synchro Time Between Inputs Depending on configuration selected
Power Consumption In W 12 W
Input Protection Type External fuse 16 A
Uc Control Circuit Voltage 28.8 V
Line Resistance 100 Ohm <6561.68 ft (2000 m)
Output Type 2 relays, 2 NO contacts (4 NO total) Solid state, 6, volt-free
Breaking Capacity 180 VA holding AC-15 C300 relay output 1800 VA inrush AC-15 C300 relay output
Breaking Capacity 2 A 24 V static output circuit 1.5 A 24 V DC-13)50 ms relay output
Output Thermal Current 4 A for both outputs simultaneously 6 A for 1 output and 2 A for the other relay output
Ith Cnvtl Free Air Therm Crrt 16 A relay output 6.5 A static output circuit
Associated Fuse Rating 16 A gL power supply 4 A gL relay output 6 A fast blow relay output
Minimum Output Current 10 mA relay output
Minimum Output Voltage 17 V relay output
Response Time Configurable : 20 ms or 30 ms with software XPSMCWIN
Ui Rated Insulation Voltage 300 V 2)IEC 60647-5-1, DIN VDE 0110 part 1
Uimp Rated Imp Wstd Voltage 4 kV III IEC 60647-5-1, DIN VDE 0110 part 1
Method Of Access Slave
Exchange Size 14 words
Number Of Addresses 1…247 Modbus
Parity Even Modbus No Modbus Odd Modbus
Data Format 1 start bit/8 data bits 1 stop bit even or odd 2 stop bits without parity RTU (Remote Terminal Unit) mode
Supported Modbus Function 01 8-bit output data/32-bit input data 02 32-bit input data/8-bit output data 03 information and errors
Local Signalling 30 LEDs
Mounting Support Mounting plate
Depth 6.02 in (153 mm)
Height 5.96 in (151.5 mm)
Width 2.91 in (74 mm)
Product Weight 1.81 lb(US) (0.82 kg)
IP Degree Of Protection IP20 EN/IEC 60529
Ambient Air Temp For Op 14…131 °F (-10…55 °C)
Ambient Air Temp For Storage -13…185 °F (-25…85 °C)
Category 22477 - SAFETY MODULES (PREVENTA)
Discount Schedule SAF2
GTIN 00785901974932
Nbr. Of Units In Pkg. 1
Country Of Origin FR
EU RoHs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury Free Yes
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews