Reversing power base, TeSys U, 3P, 32A/690V, coil 110-240V AC/DC
LU2B32FU
Reversing power base, TeSys U, 3P, 32A/690V, coil 110-240V AC/DC

TeSys U standard reversing power base, 3 poles (3NO), rated 32A/690V, to be completed with a control unit LUC to form a TeSys U reversing starter controller, for 3-phase motor applications up to 15kW@400V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a “all in one” reversing starter controller with basic or advanced protection and control functions. It is equipped with a reverser module LU2MB0FU to be supplied with 110-240V AC / 110-220V DC, auxiliary signaling contacts (1NO+1NC), a control terminal block, blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LU2B32FU
Country of Origin FR
UPC 785901454021
UPC11 78590145402
EAN 3389110363005
Availability S
Lead Time 3
UNSPSC 39121521
ECCN EAR99
HTs Code 8536200040
Prop 65 This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule I11
Return Indicator Yes
Depth 4.96 inch
Height 8.82 inch
Width 1.77 inch
Weight 2.80 pound
Characteristics
Range TeSys
Product Name TeSys U
Device Short Name LU2B
Product Or Component Type Reversing power base
Device Application Motor control Motor protection
Product Compatibility Control unit LUC.X6FU Control unit LUC.1XFU Control unit LUC.05FU Control unit LUC.12FU Control unit LUC.18FU Control unit LUC.32FU
Poles Description 3P
Suitability For ISOlation Yes
Ue Rated Operational Voltage 690 V AC power circuit
Network Frequency 40...60 Hz
Ith Cnvtl Free Air Therm Crrt 32 A
Ie Rated Operational Current 32 A <= 440 V 23 A 500 V 21 A 690 V
Utilisation Category AC-41 AC-43 AC-44
Ics Rated Service Breaking Cap 50 kA 230 V 50 kA 440 V 10 kA 500 V 4 kA 690 V
Auxiliary Contact Composition 1 NO + 1 NC
Auxiliary Contacts Type Linked contacts 1 NO + 1 NC) IEC 60947-4-1 Mirror contact 1 NC) IEC 60947-1
[Uc] Control Circuit Voltage 110...240 V AC 50/60 Hz 110...220 V DC
Ctrl Circuit Voltage Limits 55 V DC drop-out 55 V AC drop-out 88...242 V DC in operation 88...264 V AC in operation
Typical Current Consumption 1000 mA 110...220 V DC I maximum while closing 1000 mA 110...240 V AC I maximum while closing
Heat Dissipation 3 W control circuit with LUCA, LUCB, LUCC, LUCD 1.8 W control circuit with LUCM
Inrush Restraint Duration 25 ms AC 50/60 Hz 15 ms DC
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Operating Time 150 ms with change of direction power circuit 35 ms opening control circuit 75 ms without change of direction power circuit 50 ms closing control circuit
Mechanical Durability 15 Mcycles
Operating Rate 3600 cyc/h
Product Certifications CE UL CSA CCC EAC ASEFA ATEX Marine
Standards EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier
Ui Rated Insulation Voltage 690 V IEC 60947-6-2 3) 600 V UL 60947-4-1 600 V CSA C22.2 No 60947-4-1
Uimp Rated Imp Wstd Voltage 6 kVIEC 60947-6-2
Safe Separation Of Circuit 400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N
Fixing Mode Clipped DIN rail) Screw-fixed plate)
Connections - Terminals Control circuit screw clamp terminals 1 0.00…0.00 in² (0.34…1.5 mm²) flexible with cable end Control circuit screw clamp terminals 1 0.00…0.00 in² (0.75…1.5 mm²) flexible without cable end Control circuit screw clamp terminals 1 0.00…0.00 in² (0.75…1.5 mm²) rigid Control circuit screw clamp terminals 2 0.00…0.00 in² (0.34…1.5 mm²) flexible with cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (0.75…1.5 mm²) flexible without cable end Control circuit screw clamp terminals 2 0.00…0.00 in² (0.75…1.5 mm²) rigid Power circuit screw clamp terminals 1 0.00…0.02 in² (1…10 mm²) rigid Power circuit screw clamp terminals 1 0.00…0.01 in² (1…6 mm²) flexible with cable end Power circuit screw clamp terminals 1 0.00…0.02 in² (2.5…10 mm²) flexible without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) flexible with cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) rigid Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible without cable end
Tightening Torque Control circuit 7.08…10.62 lbf.in (0.8…1.2 N.m) flat 0.20 in (5 mm) Control circuit 7.08…10.62 lbf.in (0.8…1.2 N.m) Philips no 1 0.20 in (5 mm) Power circuit 16.82…22.13 lbf.in (1.9…2.5 N.m) flat 0.24 in (6 mm) Power circuit 16.82…22.13 lbf.in (1.9…2.5 N.m) Philips No 2 0.24 in (6 mm)
Width 1.77 in (45 mm)
Height 8.82 in (224 mm)
Depth 4.96 in (126 mm)
Product Weight 2.80 lb(US) (1.27 kg)
Compatibility Code LU2B
IP Degree Of Protection IP20 IEC 60947-1 front panel and wired terminals) IP20 IEC 60947-1 other faces) IP40 IEC 60947-1 front panel outside connection zone)
Protective Treatment TH IEC 60068
Ambient Air Temp For Op -13…140 °F (-25…60 °C) with LUCM -13…158 °F (-25…70 °C) with LUCA, LUCB, LUCC, LUCD
Ambient Air Temp For Storage -40…185 °F (-40…85 °C)
Fire Resistance 1760 °F (960 °C) parts supporting live components IEC 60695-2-12 1202 °F (650 °C) IEC 60695-2-12
Operating Altitude 6561.68 ft (2000 m)
Shock Resistance 10 gn power poles open IEC 60068-2-27 15 gn power poles closed IEC 60068-2-27
Vibration Resistance 2 gn 5…300 Hz) power poles open IEC 60068-2-27 4 gn 5…300 Hz) power poles closed IEC 60068-2-27
Resist Electrostatic Dischrg 8 kV 3 in open air IEC 61000-4-2 8 kV 4 on contact IEC 61000-4-2
Resistance To Radiated Fields 9.14 V/m (10 V/m) 3 IEC 61000-4-3
Resistance To Fast Transients 2 kV 3 serial link IEC 61000-4-4 4 kV 4 all circuits except for serial link IEC 61000-4-4
Non-Dissipating Shock Wave 1 kV serial mode IEC 60947-6-2 2 kV common mode IEC 60947-6-2