Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Pressure transmitter – XMLP – 100psi – 1/4″18NPT – 0..10V – M12 – set 1
XMLP100PD730
Pressure transmitter – XMLP – 100psi – 1/4″18NPT – 0..10V – M12 – set 1
Specifications
Part Number XMLP100PD730
Country of Origin CH
UPC 785901717201
UPC11 78590171720
EAN 3389119639538
Availability N
Lead Time 33
HTs Code 9026204000
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule DS2
Return Indicator Yes
Weight 0.19 pound
Characteristics
Range Of Product OsiSense XM
Product Or Component Type Electronic pressure sensors
Pressure Sensor Type Pressure transmitter
Pressure Sensor Name XMLP
Electrical Circuit Type Control circuit
Pressure Sensor Size 100 psi (689.48 kPa)
Local Display Without
Controlled Fluid Fresh water 32…275 °F (0…135 °C)) Air -40…275 °F (-40…135 °C)) Hydraulic oil -40…275 °F (-40…135 °C)) Gas -40…275 °F (-40…135 °C)) Refrigeration fluid -40…275 °F (-40…135 °C))
Fluid Connection Type 1/4" - 18 NPT (male)
Electrical Connection 1 male connector M12 4 pins
[Us] Rated Supply Voltage 24 V DC SELV 12…33 V)
Current Consumption < 7 mA
Type Of Output Signal Analogue
Analogue Output Function 0...10 V, 3-wire
Quantity Per Set Set of 1
Type Of Packing Individual
Pressure Setting Range 0…100 psi (0.00…689.48 kPa)
Max Perm Accidental Pressure 300 psi (2068.43 kPa)
Destruction Pressure 900 psi (6205.28 kPa)
Materials In Contact Wth Fluid Stainless steel AISI 316L
Operating Position Any position
Protection Type Load short-circuit Reverse polarity
Electromagnetic Compatibility Electrical fast transient/burst immunity test EN/IEC 61000-4-4 2 kV Electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 4 kV contact 1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 1 kV 42 Ohm Immunity to magnetic fields EN/IEC 61000-4-8 100 A/m 50 Hz Susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...3000 MHz Radiated RF fields EN/IEC 61000-4-6 10 V 0.01...80 MHz
Uimp Rated Imp Wstd Voltage 0.5 kV
Response Time On Output <= 2 ms 10...90 % of full scale
Measurement Accuracy +/- 0.5 % of the measuring range
Resolution 0.1 % of the measuring range
Drift Of The Sensitivity +/- 0.02 % of measuring range/°K
Drift Of The Zero Point +/- 0.02 % of measuring range/°K
Mechanical Durability 10000000 cycles
Product Weight 0.19 lb(US) (0.088 kg)
Diameter 1.02 in (26 mm)
Length 1.42 in (36 mm)
Standards NSF ANSI 61 EN/IEC 61326-2-3
Product Certifications CE EAC CULus RCM
Protective Treatment TC
Ambient Air Temp For Op -22…185 °F (-30…85 °C)
Ambient Air Temp For Storage -58…212 °F (-50…100 °C)
Vibration Resistance 20 gn 15…2000 Hz) EN/IEC 60068-2-6
Shock Resistance 100 gn 11 ms EN/IEC 60068-2-27
IP Degree Of Protection IP65 EN/IEC 60529 IP67 EN/IEC 60529 IP69K EN/IEC 60529
Category 22419 - PRESSURE SWITCH IEC (HIGH,LOW,GEN)
Discount Schedule DS2
GTIN 00785901717201
Nbr. Of Units In Pkg. 1
Country Of Origin CH
EU RoHs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury Free Yes
Documents