Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Pressure transmitter – XMEP – 7500psi – 1/4″18NPT – 0,5..4,5V – Deutsch – set 1
XMEP7K5PT130
Pressure transmitter – XMEP – 7500psi – 1/4″18NPT – 0,5..4,5V – Deutsch – set 1
Specifications
Part Number XMEP7K5PT130
Country of Origin CH
UPC 785901696780
UPC11 78590169678
EAN 3389119637046
Availability N
Lead Time 35
HTs Code 9026204000
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule DS2
Return Indicator No
Weight 0.22 pound
Characteristics
Range Of Product OsiSense XM
Product Or Component Type Electronic pressure sensors
Pressure Sensor Type Pressure transmitter
Pressure Sensor Name XMEP
Electrical Circuit Type Control circuit
Pressure Sensor Size 7500 psi (51710.68 kPa)
Local Display Without
Controlled Fluid Fresh water 32…257 °F (0…125 °C)) Air -40…257 °F (-40…125 °C)) Hydraulic oil -40…257 °F (-40…125 °C))
Fluid Connection Type 1/4" - 18 NPT (male)
Electrical Connection DEUTSCH connector DT04-3P 3 pins
[Us] Rated Supply Voltage 5 V DC SELV 4.5…5.5 V)
Current Consumption < 7 mA
Type Of Output Signal Analogue
Analogue Output Function 0.5...4.5 V, 3-wire
Quantity Per Set Set of 1
Type Of Packing Individual
Pressure Setting Range 0…7500 psi (0.00…51710.68 kPa)
Max Perm Accidental Pressure 18750 psi (129276.69 kPa)
Destruction Pressure 30000 psi (206842.71 kPa)
Materials In Contact Wth Fluid Stainless steel AISI 316L
Operating Position Any position
Protection Type Load short-circuit Reverse polarity
Electromagnetic Compatibility Electrostatic discharge immunity test ISO 10605 criteria A 15 kV air, 15 kV contact Susceptibility to electromagnetic fields ISO 11452-2 criteria A 100 V/m 200…2000 MHz Susceptibility to electromagnetic fields ISO 11452-4 criteria A 100 mA 20…400 MHz Susceptibility to conducted disturbances EN/IEC 61000-4-6 criteria A 30 V 0.15...80 MHz Electrical fast transient/burst immunity test EN/IEC 61000-4-4 criteria A 4 kV Susceptibility to conducted transient disturbances ISO 7637-2 criteria B level 3
Uimp Rated Imp Wstd Voltage 0.5 kV
Response Time On Output <= 2 ms 10...90 % of full scale
Measurement Accuracy +/- 0.5 % of the measuring range
Resolution 0.1 % of the measuring range
Drift Of The Sensitivity +/- 0.02 % of measuring range/°K
Drift Of The Zero Point +/- 0.02 % of measuring range/°K
Long Term Stability +/- 0.5 % of the measuring range
Mechanical Durability 10000000 cycles
Product Weight 0.22 lb(US) (0.098 kg)
Diameter 1.02 in (26 mm)
Length 2.50 in (63.4 mm)
Standards ISO 14982 ECE 10R-5 EN/IEC 61326-2-3 ISO 13766 UL 61010-1 EN 13309
Product Certifications E2 CE CULus
Ambient Air Temp For Op -40…212 °F (-40…100 °C)
Ambient Air Temp For Storage -58…212 °F (-50…100 °C)
Vibration Resistance 12 gn sinus 20…520 Hz)test 4 ISO 16750-3 18 gn random 10…2000 Hz)test 4 ISO 16750-3
Shock Resistance 50 gn 11 ms EN/IEC 60068-2-27
IP Degree Of Protection IP65 EN/IEC 60529 IP67 EN/IEC 60529 IP69K EN/IEC 60529
Category 22419 - PRESSURE SWITCH IEC (HIGH,LOW,GEN)
Discount Schedule DS2
GTIN 00785901696780
Nbr. Of Units In Pkg. 1
Country Of Origin CH
EU RoHs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury Free Yes
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews