Part Number | XMLD160D1S12 |
---|---|
UPC | 389110944624 |
UPC11 | 38911094462 |
EAN | 3389110944624 |
Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Depth | 3.35 inch |
Height | 4.45 inch |
Width | 1.81 inch |
Weight | 1.65 pound |
Range Of Product | OsiSense XM |
---|---|
Product Or Component Type | Electromechanical pressure sensor |
Pressure Sensor Type | Electromechanical pressure sensor |
Device Short Name | XMLD |
Pressure Sensor Size | 2320.60 psi (160 bar) |
Controlled Fluid | Hydraulic oil 32…320 °F (0…160 °C)) |
Fluid Connection Type | G 1/4 (female) ISO 228 |
Electrical Connection | Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm² |
Awg Gauge | AWG 20...AWG 14 |
Cable Entry | Cable gland 0.28…0.51 in (7…13 mm) |
Contacts Type And Composition | 2 C/O snap action, silver contacts 2 C/O staggered, silver contacts |
Product Specific Application | Dual stage |
Pressure Swt Type Of Operation | Detection of 2 single thresholds |
Electrical Circuit Type | Control circuit |
Type Of Scale | Fixed differential |
Local Display | Without |
Max Perm Accidental Pressure | 5221.36 psi (360 bar) |
Destruction Pressure | 10442.72 psi (720 bar) |
Pressure Actuator | Piston |
Materials In Contact Wth Fluid | PTFE Steel FPM, FKM Brass |
Enclosure Material | Zinc alloy |
In Rated Current | 3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1 |
Spread Between 2 Stages | 87.02…1203.81 psi (6…83 bar) |
Natural Diff At Low Setting | 127.63 psi (8.8 bar) |
Natural Diff At High Setting | 290.08 psi (20 bar) |
Max Perm Pressure - Per Cycle | 2900.75 psi (200 bar) |
Terminal Block Type | 8 terminals |
Operating Rate | 60 cyc/mn |
Repeat Accuracy | 2 % |
Ui Rated Insulation Voltage | 300 V UL 508 500 V EN/IEC 60947-1 300 V CSA C22.2 No 14 |
Uimp Rated Imp Wstd Voltage | 6 kV EN/IEC 60947-1 |
Resistance Across Terminals | 25 mOhm IEC 255-7 category 3 25 mOhm NF C 93-050 method A |
Short-Circuit Protection | 10 A cartridge fuse gG (gl) |
Mechanical Durability | 6000000 cycles |
Setting | External |
Height | 4.45 in (113 mm) |
Depth | 3.35 in (85 mm) |
Width | 1.81 in (46 mm) |
Product Weight | 1.65 lb(US) (0.75 kg) |
Standards | CSA C22.2 No 14 EN/IEC 60947-5-1 CE UL 508 |
Product Certifications | UL CSA EAC |
Protective Treatment | TC standard version |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Operating Position | Any position |
Vibration Resistance | 4 gn 30…500 Hz)IEC 60068-2-6 |
Shock Resistance | 50 gn IEC 60068-2-27 |
Electrical Shock Protect Class | Class I IEC 1140 Class I IEC 536 Class I NF C 20-030 |
IP Degree Of Protection | IP66 EN/IEC 60529 |
GTIN | 03389110944624 |