Pressure switch XMLB 500 bar – adjustable scale 2 thresholds – 1 C/O
XMLB500E2C11
Pressure switch XMLB 500 bar – adjustable scale 2 thresholds – 1 C/O
Specifications
Part Number XMLB500E2C11
UPC 389110714555
UPC11 38911071455
EAN 3389110714555
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Depth 2.95 inch
Height 4.45 inch
Width 1.38 inch
Weight 1.72 pound
Characteristics
Range Of Product OsiSense XM
Product Or Component Type Electromechanical pressure sensor
Pressure Sensor Type Electromechanical pressure sensor
Device Short Name XMLB
Pressure Sensor Size 7251.89 psi (500 bar)
Controlled Fluid Fresh water 32…320 °F (0…160 °C))
Fluid Connection Type G 1/4 (female) ISO 228
Electrical Connection 1 male connector EN 175301-803-A (ex DIN43650), 4 pins
Contacts Type And Composition 1 C/O
Pressure Swt Type Of Operation Regulation between 2 thresholds
Electrical Circuit Type Control circuit
Type Of Scale Adjustable differential
Local Display With
Adj Range High Setting 435.11…7251.89 psi (30…500 bar)
Adj Range Low Setting 101.53…6488.99 psi (7…447.4 bar)
Possible Diff Max At High Setg 4351.13 psi (300 bar)
Max Perm Accidental Pressure 16316.75 psi (1125 bar)
Destruction Pressure 32633.49 psi (2250 bar)
Pressure Actuator Piston
Materials In Contact Wth Fluid PTFE FPM, FKM Brass Stainless steel
Enclosure Material Zinc alloy
In Rated Current 3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1
Possible Diff Min At Low Setg 333.59 psi (23 bar) - 2.6 bar, + 3.8 bar)
Possible Diff Min At High Setg 762.90 psi (52.6 bar) - 14.8 bar, + 11.2 bar)
Max Perm Pressure - Per Cycle 9064.86 psi (625 bar)
Terminal Block Type 4 terminals
Operating Rate 60 cyc/mn
Repeat Accuracy 2 %
Ui Rated Insulation Voltage 300 V UL 508 500 V EN/IEC 60947-1 300 V CSA C22.2 No 14
Uimp Rated Imp Wstd Voltage 6 kV EN/IEC 60947-1
Auxiliary Contacts Operation Snap action
Contacts Material Silver contacts
Resistance Across Terminals 25 mOhm IEC 255-7 category 3 25 mOhm NF C 93-050 method A
Short-Circuit Protection 10 A cartridge fuse gG (gl)
Mechanical Durability 3000000 cycles
Setting External
Height 4.45 in (113 mm)
Depth 2.95 in (75 mm)
Width 1.38 in (35 mm)
Product Weight 1.72 lb(US) (0.78 kg)
Standards EN/IEC 60947-5-1 CSA C22.2 No 14 CE UL 508
Product Certifications UL EAC LROS (Lloyds register of shipping) BV CCC CSA
Protective Treatment TC standard version
Ambient Air Temp For Op -13…158 °F (-25…70 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Operating Position Any position
Vibration Resistance 4 gn 30…500 Hz)IEC 60068-2-6
Shock Resistance 50 gn IEC 60068-2-27
Electrical Shock Protect Class Class I IEC 1140 Class I IEC 536 Class I NF C 20-030
IP Degree Of Protection IP65 EN/IEC 60529