This 300bar pressure switch is part of the XML range, an offer of electromechanical pressure and vacuum switches. These switches have an adjustable differential and are designed for regulation between two thresholds. The function of pressure switches is the control or regulation of pressure levels in hydraulic systems. They transform the pressure change into a digital electrical signal when the preset switching points are reached. This pressure switch has a setting scale and an adjustable range of switching point, or rising pressure, from22bar to 300bar (319psi to 4350psi). Thanks to the electromechanical technology, this product is reliable and simple to use. It incorporates one C/O single-pole contact, snap action. It has a piston pressure actuator. This pressure switch features a zinc alloy case, a G 1/4 female fluid connector and one entry tapped M20 x 1.5mm for ISO gable gland. Electrical connection with screw-clamps terminals. It is suitable for controlling corrosive fluids and air up to +160°C. It complies with UL, CSA, EAC, CCC,BV, LROS certifications, and with CE, IEC/EN 60947-5-1, UL 508, CSA C22-2 no. 14 standards. Dedicated accessories, to be ordered separatly, are available to facilitate the setting or ptotect the switch. Knurled adjustment knob, fixing plate, lead sealable protective cover, sealing gaskets, etc. The XML range brings high level of reliability and quality, long life duration, and a worldwide availability.
Brand: Telemecanique
Add to Quote CataloguePart Number | XMLB300N2S12 |
---|---|
UPC | 389110757323 |
UPC11 | 38911075732 |
EAN | 3389110757323 |
Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Depth | 2.95 inch |
Height | 4.45 inch |
Width | 1.38 inch |
Weight | 1.65 pound |
Range Of Product | OsiSense XM |
---|---|
Product Or Component Type | Electromechanical pressure sensor |
Pressure Sensor Type | Electromechanical pressure sensor |
Device Short Name | XMLB |
Pressure Sensor Size | 4351.13 psi (300 bar) |
Controlled Fluid | Air 32…320 °F (0…160 °C)) Corrosive fluid 32…320 °F (0…160 °C)) |
Fluid Connection Type | G 1/4 (female) ISO 228 |
Electrical Connection | Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm² |
Awg Gauge | AWG 20...AWG 14 |
Cable Entry | Cable gland 0.28…0.51 in (7…13 mm) |
Contacts Type And Composition | 1 C/O |
Pressure Swt Type Of Operation | Regulation between 2 thresholds |
Electrical Circuit Type | Control circuit |
Type Of Scale | Adjustable differential |
Local Display | With |
Adj Range High Setting | 319.08…4351.13 psi (22…300 bar) |
Adj Range Low Setting | 37.71…3814.49 psi (2.6…263 bar) |
Possible Diff Max At High Setg | 2900.75 psi (200 bar) |
Max Perm Accidental Pressure | 9790.05 psi (675 bar) |
Destruction Pressure | 19580.10 psi (1350 bar) |
Pressure Actuator | Piston |
Materials In Contact Wth Fluid | PTFE FPM, FKM 316L stainless steel |
Enclosure Material | Zinc alloy |
In Rated Current | 3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1 |
Possible Diff Min At Low Setg | 281.37 psi (19.4 bar) - 1.5 bar, + 1.7 bar) |
Possible Diff Min At High Setg | 536.64 psi (37 bar) - 1 bar, + 4 bar) |
Max Perm Pressure - Per Cycle | 5438.92 psi (375 bar) |
Terminal Block Type | 4 terminals |
Operating Rate | 60 cyc/mn |
Repeat Accuracy | 2 % |
Ui Rated Insulation Voltage | 300 V UL 508 500 V EN/IEC 60947-1 300 V CSA C22.2 No 14 |
Uimp Rated Imp Wstd Voltage | 6 kV EN/IEC 60947-1 |
Auxiliary Contacts Operation | Snap action |
Contacts Material | Silver contacts |
Resistance Across Terminals | 25 mOhm IEC 255-7 category 3 25 mOhm NF C 93-050 method A |
Short-Circuit Protection | 10 A cartridge fuse gG (gl) |
Mechanical Durability | 3000000 cycles |
Setting | External |
Height | 4.45 in (113 mm) |
Depth | 2.95 in (75 mm) |
Width | 1.38 in (35 mm) |
Product Weight | 1.65 lb(US) (0.75 kg) |
Standards | CE UL 508 EN/IEC 60947-5-1 CSA C22.2 No 14 |
Product Certifications | CCC BV UL EAC LROS (Lloyds register of shipping) CSA |
Protective Treatment | TC standard version |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Operating Position | Any position |
Vibration Resistance | 4 gn 30…500 Hz)IEC 60068-2-6 |
Shock Resistance | 50 gn IEC 60068-2-27 |