Part Number | XMLA300E2S11 |
---|---|
UPC | 389110712308 |
UPC11 | 38911071230 |
EAN | 3389110712308 |
Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Depth | 2.95 inch |
Height | 4.45 inch |
Width | 1.38 inch |
Weight | 1.65 pound |
Range Of Product | OsiSense XM |
---|---|
Product Or Component Type | Electromechanical pressure sensor |
Pressure Sensor Type | Electromechanical pressure sensor |
Device Short Name | XMLA |
Pressure Sensor Size | 4351.13 psi (300 bar) |
Controlled Fluid | Fresh water 32…320 °F (0…160 °C)) |
Fluid Connection Type | G 1/4 (female) ISO 228 |
Electrical Connection | Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm² |
Awg Gauge | AWG 20...AWG 14 |
Cable Entry | Cable gland 0.35…0.51 in (9…13 mm) |
Contacts Type And Composition | 1 C/O |
Pressure Swt Type Of Operation | Detection of 1 single threshold |
Electrical Circuit Type | Control circuit |
Type Of Scale | Fixed differential |
Local Display | With |
Adj Range High Setting | 290.08…4351.13 psi (20…300 bar) |
Adj Range Low Setting | 50.76…3843.50 psi (3.5…265 bar) |
Max Perm Accidental Pressure | 9790.05 psi (675 bar) |
Destruction Pressure | 19580.10 psi (1350 bar) |
Pressure Actuator | Piston |
Materials In Contact Wth Fluid | FPM, FKM PTFE 316L stainless steel Brass |
Enclosure Material | Zinc alloy |
In Rated Current | 3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1 |
Natural Diff At Low Setting | 239.31 psi (16.5 bar) +/- 3 bar) |
Natural Diff At High Setting | 507.63 psi (35 bar) +/- 6 bar) |
Max Perm Pressure - Per Cycle | 5438.92 psi (375 bar) |
Terminal Block Type | 4 terminals |
Operating Rate | 60 cyc/mn |
Repeat Accuracy | 2 % |
Ui Rated Insulation Voltage | 300 V UL 508 500 V EN/IEC 60947-1 300 V CSA C22.2 No 14 |
Uimp Rated Imp Wstd Voltage | 6 kV EN/IEC 60947-1 |
Auxiliary Contacts Operation | Snap action |
Contacts Material | Silver contacts |
Resistance Across Terminals | 25 mOhm IEC 255-7 category 3 25 mOhm NF C 93-050 method A |
Short-Circuit Protection | 10 A cartridge fuse gG (gl) |
Mechanical Durability | 3000000 cycles |
Setting | External |
Height | 4.45 in (113 mm) |
Depth | 2.95 in (75 mm) |
Width | 1.38 in (35 mm) |
Product Weight | 1.65 lb(US) (0.75 kg) |
Standards | CE IEC 60947-5-1 UL 508 EN 60947-5-1 EN/IEC 60947-5-1 CSA C22.2 No 14 |
Product Certifications | LROS (Lloyds register of shipping) CSA EAC CCC UL BV |
Protective Treatment | TC standard version |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Operating Position | Any position |
Vibration Resistance | 4 gn 30…500 Hz)IEC 60068-2-6 |
Shock Resistance | 50 gn IEC 60068-2-27 |
Electrical Shock Protect Class | Class I IEC 1140 Class I IEC 536 Class I NF C 20-030 |