This 10bar pressure switch is part of the XML range, an offer of electromechanical pressure and vacuum switches. This switch has a fixed differential and is designed for detection of a single threshold. The function of pressure switches is the control or regulation of pressure levels in hydraulic systems. They transform the pressure change into a digital electrical signal when the preset switching points are reached. This pressure switch has a setting scale and an adjustable range of switching point, or rising pressure, from 0.6bar to 10bar (8.7psi to 145psi). Thanks to the electromechanical technology, this product is reliable and simple to use. It incorporates one C/O single-pole contact, snap action. It has a diaphragm pressure actuator. This pressure switch features a zinc alloy case, a G 1/4 female fluid connector and one entry tapped for n°13 gable gland. Electrical connection with screw-clamps terminals. It is suitable for controlling corrosive fluids up to +160°C and sea water up to +30°C. It complies with UL, CSA, EAC, CCC, BV, LROS certifications, and with CE, IEC/EN 60947-5-1, UL 508, CSA C22-2 no. 14 standards. Dedicated accessories, to be ordered separatly, are available to facilitate the setting or ptotect the switch. Knurled adjustment knob, fixing plate, lead sealable protective cover, sealing gaskets, etc. This switch operates in all positions. The XML range brings high level of reliability and quality, long life duration, and a worldwide availability.
Brand: Telemecanique
Add to Quote CataloguePart Number | XMLA010C2S11 |
---|---|
Country of Origin | CZ |
UPC | 389110711615 |
UPC11 | 38911071161 |
EAN | 3389110711615 |
Availability | N |
Lead Time | 21 |
UNSPSC | 39122210 |
ECCN | EAR99 |
HTs Code | 9032200000 |
Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | DS2 |
Return Indicator | No |
Depth | 2.95 inch |
Height | 4.45 inch |
Width | 1.38 inch |
Weight | 1.51 pound |
Range Of Product | OsiSense XM |
---|---|
Product Or Component Type | Electromechanical pressure sensor |
Pressure Sensor Type | Electromechanical pressure sensor |
Device Short Name | XMLA |
Pressure Sensor Size | 145.04 psi (10 bar) |
Controlled Fluid | Corrosive fluid 32…320 °F (0…160 °C)) |
Fluid Connection Type | G 1/4 (female) ISO 228 |
Electrical Connection | Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm² 1 connector Pg 13 |
Awg Gauge | AWG 20...AWG 14 |
Cable Entry | Cable gland 0.35…0.51 in (9…13 mm) |
Contacts Type And Composition | 1 C/O |
Pressure Swt Type Of Operation | Detection of 1 single threshold |
Electrical Circuit Type | Control circuit |
Type Of Scale | Fixed differential |
Local Display | With |
Adj Range High Setting | 8.70…145.04 psi (0.6…10 bar) |
Adj Range Low Setting | 1.45…137.79 psi (0.1…9.5 bar) |
Max Perm Accidental Pressure | 326.33 psi (22.5 bar) |
Destruction Pressure | 652.67 psi (45 bar) |
Pressure Actuator | Diaphragm |
Materials In Contact Wth Fluid | PTFE 316L stainless steel |
Enclosure Material | Zinc alloy |
In Rated Current | 3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1 |
Natural Diff At Low Setting | 7.25 psi (0.5 bar) +/- 0.05 bar) |
Natural Diff At High Setting | 7.25 psi (0.5 bar) +/- 0.05 bar) |
Max Perm Pressure - Per Cycle | 181.30 psi (12.5 bar) |
Terminal Block Type | 4 terminals |
Operating Rate | 120 cyc/mn |
Repeat Accuracy | 2 % |
Ui Rated Insulation Voltage | 300 V UL 508 500 V EN/IEC 60947-1 300 V CSA C22.2 No 14 |
Uimp Rated Imp Wstd Voltage | 6 kV EN/IEC 60947-1 |
Auxiliary Contacts Operation | Snap action |
Contacts Material | Silver contacts |
Resistance Across Terminals | 25 mOhm IEC 255-7 category 3 25 mOhm NF C 93-050 method A |
Short-Circuit Protection | 10 A cartridge fuse gG (gl) |
Mechanical Durability | 5000000 cycles |
Setting | External |
Height | 4.45 in (113 mm) |
Depth | 2.95 in (75 mm) |
Width | 1.38 in (35 mm) |
Product Weight | 1.51 lb(US) (0.685 kg) |
Standards | CE UL 508 EN/IEC 60947-5-1 CSA C22.2 No 14 |
Product Certifications | CSA UL EAC CCC LROS (Lloyds register of shipping) BV |
Protective Treatment | TC standard version |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Operating Position | Any position |
Vibration Resistance | 4 gn 30…500 Hz)IEC 60068-2-6 |
Shock Resistance | 50 gn IEC 60068-2-27 |
Electrical Shock Protect Class | Class I IEC 1140 Class I IEC 536 Class I NF C 20-030 |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366