This XMLA electromechanical pressure switch has a fixed differential for detection of a single threshold and a zinc alloy body with a range scale window. This pressure switch is designed for detection of a single pressure threshold in air and hydraulic oils up to 160°C. It is fixed directly on tubage. It provides 304L stainless steel fitting for maximum corrosion and thermal shock resistance. 4 million cycles mechanical durability for minimum required maintenance on your pressurized fluid circuits. It complies with CCC, EN/IEC 60947-5-1, CSA C22.2 No.14, LROS, UL 508, EAC, BV.
Brand: Telemecanique
Add to Quote CataloguePart Number | XMLA001R2S12 |
---|---|
Country of Origin | CZ |
UPC | 785901655039 |
UPC11 | 78590165503 |
EAN | 3389110748215 |
Availability | N |
Lead Time | 20 |
UNSPSC | 39122210 |
ECCN | EAR99 |
HTs Code | 9032200000 |
Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | DS2 |
Return Indicator | No |
Depth | 4.33 inch |
Height | 6.38 inch |
Width | 4.33 inch |
Weight | 5.63 pound |
Range Of Product | OsiSense XM |
---|---|
Product Or Component Type | Electromechanical pressure sensor |
Pressure Sensor Type | Electromechanical pressure sensor |
Device Short Name | XMLA |
Pressure Sensor Size | 14.50 psi (1 bar) |
Controlled Fluid | Air 32…320 °F (0…160 °C)) Hydraulic oil 32…320 °F (0…160 °C)) |
Fluid Connection Type | G 1/4 (female) ISO 228 |
Electrical Connection | Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm² 1 connector ISO M20 |
Awg Gauge | AWG 20...AWG 14 |
Cable Entry | Cable gland 0.28…0.51 in (7…13 mm) |
Contacts Type And Composition | 1 C/O |
Pressure Swt Type Of Operation | Detection of 1 single threshold |
Electrical Circuit Type | Control circuit |
Type Of Scale | Fixed differential |
Local Display | With |
Adj Range High Setting | 0.44…14.50 psi (0.03…1 bar) |
Adj Range Low Setting | 0.15…13.92 psi (0.01…0.96 bar) |
Max Perm Accidental Pressure | 32.63 psi (2.25 bar) |
Destruction Pressure | 65.27 psi (4.5 bar) |
Pressure Actuator | Diaphragm |
Materials In Contact Wth Fluid | 304L stainless steel Steel FPM, FKM |
Enclosure Material | Zinc alloy |
In Rated Current | 3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1 |
Natural Diff At Low Setting | 0.29 psi (0.02 bar) +/- 0.01 bar) |
Natural Diff At High Setting | 0.58 psi (0.04 bar) +/- 0.01 bar) |
Max Perm Pressure - Per Cycle | 18.13 psi (1.25 bar) |
Terminal Block Type | 4 terminals |
Operating Rate | 120 cyc/mn |
Repeat Accuracy | 2 % |
Ui Rated Insulation Voltage | 300 V UL 508 500 V EN/IEC 60947-1 300 V CSA C22.2 No 14 |
Uimp Rated Imp Wstd Voltage | 6 kV EN/IEC 60947-1 |
Auxiliary Contacts Operation | Snap action |
Contacts Material | Silver contacts |
Resistance Across Terminals | 25 mOhm IEC 255-7 category 3 25 mOhm NF C 93-050 method A |
Short-Circuit Protection | 10 A cartridge fuse gG (gl) |
Mechanical Durability | 4000000 cycles |
Setting | External |
Height | 6.38 in (162 mm) |
Depth | 4.33 in (110 mm) |
Width | 4.33 in (110 mm) |
Product Weight | 5.63 lb(US) (2.555 kg) |
Standards | CE EN/IEC 60947-5-1 CSA C22.2 No 14 UL 508 |
Product Certifications | CCC BV LROS (Lloyds register of shipping) CSA EAC UL |
Protective Treatment | TC standard version |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Operating Position | Any position |
Vibration Resistance | 2 gn 30…500 Hz)IEC 60068-2-6 |
Shock Resistance | 30 gn IEC 60068-2-27 |
Electrical Shock Protect Class | Class I IEC 1140 Class I IEC 536 Class I NF C 20-030 |