This XMLR electronic pressure sensor has a 4 digit 7-segment display. This electronic pressure transmitter sensor with digital display is designed for accurate pressure measurement and display. It is fixed directly on tubage. It provides high corrosion resistance AISI 316L stainless steel and fluorocarbon resin pressure chamber for maximum longevity. 10 million cycles mechanical durability for minimum required maintenance on your pressurized fluid circuits. It has a supply voltage of 24V DC, 2 x solid state outputs (PNP) and an analog ouput of 4mA to 20mA. It provides IP65/IP67 degree of protection. It is ideal in moulding and thermoforming presses, injection machines, pneumatic systems and assembly machinery, hydraulic systems of lifting and handling equipment, pumping and fresh water treatment. It complies with EN/IEC 61326-2-3 and UL 61010-1.
Brand: Telemecanique
Add to Quote CataloguePart Number | XMLRM01G2P25 |
---|---|
Country of Origin | CH |
UPC | 389119609876 |
UPC11 | 38911960987 |
EAN | 3389119609876 |
Availability | N |
Lead Time | 35 |
ECCN | EAR99 |
HTs Code | 9032200000 |
Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | DS2 |
Return Indicator | No |
Depth | 1.65 inch |
Height | 3.66 inch |
Width | 1.61 inch |
Weight | 0.42 pound |
Range Of Product | OsiSense XM |
---|---|
Product Or Component Type | Electronic pressure sensors |
Pressure Sensor Type | Pressure transmitter |
Pressure Swt Type Of Operation | Pressure transmitter with 2 switching outputs |
Device Short Name | XMLR |
Pressure Sensor Size | -14.5 psi (-99.97 kPa) -14.50 psi (-1 bar) |
Max Perm Accidental Pressure | 43.51 psi (3 bar) 43 psi (296.47 kPa) 43.51 psi (300 kPa) |
Destruction Pressure | 43 psi (296.47 kPa) 43.51 psi (300 kPa) 43.51 psi (3 bar) |
Controlled Fluid | Fresh water 32…176 °F (0…80 °C)) Air -4…176 °F (-20…80 °C)) Hydraulic oil -4…176 °F (-20…80 °C)) Refrigeration fluid -4…176 °F (-20…80 °C)) |
Fluid Connection Type | G 1/4 (female) DIN 3852-Y |
[Us] Rated Supply Voltage | 24 V DC SELV 17…33 V) |
Current Consumption | <= 50 mA |
Electrical Connection | Male connector M12, 5 pins |
Analogue Output Function | 4...20 mA |
Type Of Output Signal | Analogue + discrete |
Discrete Output Type | Solid state PNP, 2 NO/NC programmable |
Maximum Switching Current | 250 mA |
Contacts Type And Composition | 2 NO/NC programmable |
Type Of Scale | Fixed differential |
Voltage Drop | 2 V |
Adj Range High Setting | -14.5…-1.16 psi (-99.97…-8.00 kPa) -14.50…-1.16 psi (-100…-8 kPa) -14.50…-1.16 psi (-1…-0.08 bar) |
Adj Range Low Setting | -14.07…0.73 psi (-97…5 kPa) -14.1…-0.73 psi (-97.22…-5.03 kPa) -14.07…-0.73 psi (-0.97…-0.05 bar) |
Minimum Differential Travel | 0.43 psi (2.96 kPa) 0.44 psi (0.03 bar) 0.44 psi (3 kPa) |
Materials In Contact Wth Fluid | Fluorocarbon FKM (Viton) 316L stainless steel Ceramic |
Front Material | Polyester |
Housing Material | Polyacrylamide 316L stainless steel |
Operating Position | Any position, but disposals can falsified the measurement in case of upside down mounting |
Protection Type | Overload protection Short-circuit protection Overvoltage protection Reverse polarity |
Response Time On Output | <= 10 ms analog output <= 5 ms discrete output |
Switching Output Time Delay | 0...50 s in steps of 1 second |
Display Type | 4 digits 7 segments |
Local Signalling | Light ON when switch is actuated 2 LEDs yellow) |
Display Response Time Type | Fast 50 ms Normal 200 ms Slow 600 ms |
Delay First Up | 300 ms |
Overall Accuracy | <= 1 % of the measuring range |
Linearity Error On Analogue Output | <= 0.5 % of the measuring range |
Hysteresis On Analogue Output | <= 0.2 % of the measuring range |
Measurement Accuracy On Switching Output | <= 0.6 % of the measuring range |
Repeat Accuracy | <= 0.2 % of the measuring range |
Drift Of The Sensitivity | +/- 0.03 % of measuring range/°C |
Drift Of The Zero Point | +/- 0.1 % of measuring range/°C |
Display Accuracy | <= 1 % of the measuring range |
Mechanical Durability | 10000000 cycles |
Depth | 1.65 in (42 mm) |
Height | 3.66 in (93 mm) |
Width | 1.61 in (41 mm) |
Product Weight | 0.42 lb(US) (0.19 kg) |
Uimp Rated Imp Wstd Voltage | 0.5 kV DC |
Electromagnetic Compatibility | Susceptibility to electromagnetic fields 10 V/m 80...2000 MHz EN/IEC 61000-4-3 Immunity to conducted RF disturbances 10 V 0.15...80 MHz EN/IEC 61000-4-6 Surge immunity test 1 kV EN/IEC 61000-4-5 Electrical fast transient/burst immunity test 2 kV EN/IEC 61000-4-4 Electrostatic discharge immunity test 8 kV air, 4 kV contact EN/IEC 61000-4-2 |
Marking | CE |