This PowerPact Multistandard L frame molded case circuit breaker has 3 poles, is unit mounted, and has a line rated current rating of 600 A at 40 °C. It comes with a Micrologic 3.0 electronit trip unit providing LI protection and has a breaking capacity of 14 kA at 600 V AC per UL 489 and 14 kA at 500/525 V AC per IEC 947-2. These circuit breakers have an over center, trip-free toggle mechanism with quick make, quick break action. The circuit breaker handle can assume any of three positions, ON, tripped or OFF with a positive visual indication if the circuit breakers has tripped and interrupted the circuit. All PowerPact Multistandard circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. Powerpact Multistandard L frame circuit breakers come with metric terminal nuts on the device line and load side. The device dimensions are height 287.02 mm, width 139.70 mm, depth 167.89 mm. Common accessories and auxiliaries are available within the PowerPact range of molded case circuit breakers Powerpact Multistandard circuit breakers are certified by UL, CSA, NOM, IEC, CCC, and CE marked for global acceptance
Brand: Square D
Add to Quote CataloguePart Number | NLDF36600U31XTW |
---|---|
Country of Origin | US |
UPC | 785901874997 |
UPC11 | 78590187499 |
EAN | 0785901874997 |
Availability | N |
UNSPSC | 39121601 |
ECCN | EAR99 |
HTs Code | 8536200020 |
Prop 65 | This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | DE2 |
Return Indicator | No |
Depth | 4.33 inch |
Height | 13.39 inch |
Width | 5.51 inch |
Weight | 13.67 pound |
Range Of Product | PowerPact multistandard |
---|---|
Range | PowerPact |
Product Name | L-Frame |
Device Short Name | L-Frame |
Product Or Component Type | Circuit breaker |
Device Application | Distribution |
Poles Description | 3P |
Control Type | Toggle |
Mounting Mode | Unit mount |
Mounting Support | DIN rail Backplate Flush |
Electrical Connection | Terminal nut line side Terminal nut load side |
In Rated Current | 600 A 104 °F (40 °C) |
Ui Rated Insulation Voltage | 750 V AC 50/60 Hz IEC 60947-2 |
Uimp Rated Imp Wstd Voltage | 8 kV IEC 60947-2 |
Ue Rated Operational Voltage | 525 V AC 50/60 Hz IEC 60947-2 690 V AC 50/60 Hz IEC 947-2 600 V AC 50/60 Hz UL 489 |
Rating Code | LD |
Suitability For ISOlation | Yes |
Utilisation Category | Category A |
Mechanical Durability | 5000 cycles |
Electrical Durability | 1000 cycles |
Connection Pitch | 1.77 in (45 mm) |
Local Signalling | ON/OFF indication |
Contact Position Indicator | Yes |
Trip Unit Name | Micrologic 3.0 |
Trip Unit Technology | Electronic |
Trip Unit Protection Functions | LI |
Trip Unit Rating | 600 A |
Thermal Memory | 20 mn |
Display Type | 3 LEDs |
Breaking Capacity | Icu 25 kA 220/240 V - AC IEC 947-2 Icu 18 kA 380/415 V - AC IEC 947-2 Icu 18 kA 440/480 V - AC IEC 947-2 Icu 14 kA 500/525 V - AC IEC 947-2 25 kA 240 V - AC UL 489 18 kA 480 V - AC UL 489 14 kA 600 V - AC UL 489 |
Ics Rated Service Breaking Cap | Ics 25 kA 220/240 V - AC IEC 947-2 Ics 18 kA 380/415 V - AC IEC 947-2 Ics 18 kA 440/480 V - AC IEC 947-2 Ics 14 kA 500/525 V - AC IEC 947-2 |
Lg Time Pick Up Adj Type Ir | Adjustable 9 settings |
Long Time Pick-Up Adjust Rng | 0.33...1 x In |
Tr Long-Time Delay Adjust Rng | 8 s 4 s 16 s 0.5 s 2 s 1 s |
Instt Pick Up Adj Type Ii | Adjustable 9 settings |
Instant Pick-Up Adj Range | 1.5...15 x In |
Overvoltage Category | II |
Provision For Padlocking | Non padlockable |
Height | 13.39 in (340 mm) |
Width | 5.51 in (140 mm) |
Depth | 4.33 in (110 mm) |
Standards | NMX J-266 UL 489 NEMA AB1 W-C-375B/GEN IEC 60947-2 CSA C22.2 No 5 |
Product Certifications | CCC CE |
Product Weight | 13.67 lb(US) (6.2 kg) |
Tightening Torque | 442.54 lbf.in (50 N.m) |
IP Degree Of Protection | IP40 IEC 60529 |
IK Degree Of Protection | IK07 IEC 62262 |
Pollution Degree | 3 IEC 60947-1 3 IEC 60664-1 |
Ambient Air Temp For Op | 104 °F (40 °C) |
Ambient Air Temp For Storage | -58…185 °F (-50…85 °C) |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366