PowerPact B-frame circuit breaker, offers proven performance, flexibility, and reliability. This PowerPact Molded Case Circuit Breaker feature new innovations such as the patented EverLink™ connections. PowerPact B-frame circuit breakers provides economical thermal magnetic circuit protection with a breaking capacity of 25kA at 220 / 240 VAC50/60 Hz. PowerPact B-frame circuit breakers come in 1 to 4-pole unit mount construction also 1 to 3-pole I-Line construction. This PowerPact B, 90A, 3P, circuit breaker has a breaking capacity of 14kA@600Y/347VAC@50/60 Hz per UL 489 standards. This circuit breaker has a thermal-magnetic trip unit technology with a mechanical service life of and an electrical service life of @440V. This clip-on breaker has a presence of auxiliary contacts green signaling function. The I-Line lug can accept an AWG gauge AWG 6 / AWG 2/0, aluminium/copper. This breakers complies to UL, IEC, CCC, EAC, CSA, NOM standards. Powerpact B-Frame breakers have an operating altitude test condition of 2000 m without derating and a 5000 m with derating. Dimensions for this product are 137 mm (H),54 mm (W),80 mm (D) and a weight of 0.769kg. This breaker has a continuous current rating of 80%.
Brand: Square D
Add to Quote CataloguePart Number | BDL36090LW |
---|---|
Country of Origin | US |
Availability | N |
UNSPSC | 39121601 |
Discount Schedule | DE2 |
Return Indicator | No |
Range | PowerPact |
---|---|
Product Name | PowerPact B |
Device Short Name | BD 090 |
Product Or Component Type | Circuit breaker |
Device Application | Distribution |
Accessory / Separate Part Type | Control wire |
Number Of Poles | 3P |
Control Type | Toggle |
Rating Code | D |
Breaking Capacity | 25 kA 208Y/120 V AC 50/60 Hz UL 489 25 kA 240 V AC 50/60 Hz UL 489 18 kA 480/277 V AC 50/60 Hz UL 489 18 kA 480 V AC 50/60 Hz UL 489 14 kA 600Y/347 V AC 50/60 Hz UL 489 10 kA 250 V DC UL 489 |
Ue Rated Operational Voltage | 525 V AC 50/60 Hz UL 489 |
Ics Rated Service Breaking Cap | 25 kA 220...240 V AC 50/60 Hz IEC 60947-2 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 18 kA 440 V AC 50/60 Hz IEC 60947-2 |
Uimp Rated Imp Wstd Voltage | 8 kV IEC 60947-2 |
Ui Rated Insulation Voltage | 800 V IEC 60947-2 |
Trip Unit Technology | Thermal-magnetic |
Suitability For ISOlation | Yes IEC 60947-2 |
Utilisation Category | Category A |
Mechanical Durability | IEC 947-1 Annex K ed 5.2 |
Electrical Durability | 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In |
Local Signalling | Presence of auxiliary contacts flag green) |
Mounting Mode | Clip-on 35 x 15 mm symmetrical DIN rail) By screws plate) |
Electrical Connection | Everlink lug line Everlink lug load |
Awg Gauge | AWG 6...AWG 2/0 fine stranded copper AWG 14...AWG 3/0 rigid or stranded copper |
Tightening Torque | 44.25 lbf.in (5 N.m) 0.00…0.02 in² (2.5…16 mm²) AWG 14...AWG 4) 79.66 lbf.in (9 N.m) 0.04…0.15 in² (25…95 mm²) AWG 3...AWG 3/0) |
Number Of Slots | auxiliary switch OF plug-in) voltage release MN or MX plug-in) alarm switch SD plug-in) |
Color | Gray RAL 7016) |
Quantity Per Set | Set of 1 |
Continuous Current Rating | 80 % |
Quality Labels | CE |
Standards | NEMA AB1 CSA C22.2 No 5 EN/IEC 60947-2 NMX J-266 GB 14048.2 EN/IEC 60947-5-1 UL 489 |
Product Certifications | UL IEC CCC EAC CSA NOM |
IP Degree Of Protection | Front cover IP40 IEC 60529 |
IK Degree Of Protection | IK07 IEC 62262 |
Pollution Degree | 3 IEC 60947-1 |
Operating Altitude | < 6561.68 ft (2000 m) without derating 5000 m with derating |
Category | 01130 - BD UNIT MOUNT BREAKER/SWITCH |
Discount Schedule | DE2 |
Country Of Origin | US |