Part Number | LGL46000S60X |
---|---|
UNSPSC | 39121601 |
Prop 65 | This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Return Indicator | Yes |
Depth | 6.61 inch |
Height | 13.38 inch |
Width | 5.51 inch |
Product Or Component Type | Automatic switch |
---|---|
Range Of Product | PowerPact L |
Trip Unit Technology | Magnetic |
Circuit Breaker Type | L-Frame |
In Rated Current | 600 A |
Ue Rated Operational Voltage | 600 V AC |
Mounting Mode | Unit mount |
Poles Description | 4P |
Short-Circuit Withstand | 65 kA 240 V UL 489 35 kA 480 V UL 489 18 kA 600 V UL 489 |
Rating Code | G |
Electrical Connection | Lugs line Lugs load |
Awg Gauge | AWG 2/0...500 kcmil aluminium/copper) |
Terminal Identifier | AL600LS52K4 |
Magnetic Tripping Current | 6600 A |
Height | 13.38 in (339.85 mm) |
Width | 5.51 in (139.95 mm) |
Depth | 6.61 in (167.89 mm) |
Tightening Torque | 442.54 lbf.in (50 N.m) 0.11…0.37 in² (70…240 mm²) AWG 2/0...500 kcmil) |
Product Certifications | UL Listed CSA IEC |
Category | 01116-L ELEC TRIP UNIT MOUNT BREAKER/SW |
Discount Schedule | DE2 |
Country Of Origin | US |
Green Premium Status | Green Premium product |
EU RoHs Directive | Compliant |
Mercury Free | Yes |
Pvc Free | Yes |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366