Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Power interface module, TeSys island, 15A AC-1, 9A AC-3, 4kW / 5hp
TPRPM009
Power interface module, TeSys island, 15A AC-1, 9A AC-3, 4kW / 5hp

TeSys island power module, 3 poles, 9A/690V. Connected to a TPRBC bus coupler it protects and monitors loads up to 9A and motors up to 4kW@400V / 5hp@480V. External power switching devices could be controlled if associated to a digital IO module TPRDG4X2. It provides motor protection functions including thermal overload (setting 0.18-9A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number TPRPM009
EAN 3606489832841
Availability N
Lead Time 20
ECCN EAR99
HTs Code 8537109170
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 4.53 inch
Height 4.76 inch
Width 1.77 inch
Weight 0.56 pound
Characteristics
Range Of Product TeSys
Product Name TeSys island
Device Short Name TPRPM
Product Or Component Type Power module
Device Presentation Power module connected to an automation controller through a bus coupler Operational only when connected to a bus coupler
Function Available Upstream voltage presence detection Electronic thermal overload protection Monitoring of currents Control of third party power devices when associated to TPRDG IO module
Product Compatibility TPRBC bus coupler TPRDG digital IO module TPRAN analog IO module
Poles Description 3P
Motor Power kW 2.2 kW 230 V AC 50 Hz 4 kW 380...415 V AC 50 Hz 4 kW 440 V AC 50 Hz 5.5 kW 500 V AC 50 Hz 5.5 kW 690 V AC 50 Hz
Motor Power Hp (Ul / Csa) 0.33 hp 120 V AC 60 Hz 1 phase 1 hp 240 V AC 60 Hz 1 phase 2 hp 208 V AC 60 Hz 3 phase 2 hp 240 V AC 60 Hz 3 phase 5 hp 480 V AC 60 Hz 3 phase 7.5 hp 600 V AC 60 Hz 3 phase
Ue Rated Operational Voltage <= 690 V AC 47...63 Hz
Ie Rated Operational Current 9 A 122 °F (50 °C)) <= 440 V AC-3 15 A 122 °F (50 °C)) <= 440 V AC-1
Ith Cnvtl Free Air Therm Crrt 15 A 122 °F (50 °C)
Ui Rated Insulation Voltage 690 V IEC 60947-4-1 600 V UL 60947-4-1 600 V CSA C22.2 No 60947-4-1
Uimp Rated Imp Wstd Voltage 6 kV
Overvoltage Category III
Thermal Protection Adj Range 0.18…9 A
Thermal Overload Class Class 5…30
Reset Remotely or automatically
Uc Control Circuit Voltage 24 V DC supplied by the bus coupler
Current Consumption 60 mA
Power Dissipation In W 0.6 W at Ie
Protection Type Thermal overload protection Motor overheat Overcurrent Undercurrent Jam Long start Stall Rapid cycle lockout Phase loss Rapid restart lockout Phase reversal Phase unbalance Phase sequence Ground current
Monitoring Type Time device ON Number of faults Number of device power cycles Average current Iavg Average voltage Vavg Max current Imax Max voltage Vmax
Local Signalling DS (device status) 1 LED green/red) LS (load status) 1 LED green/red)
Standards EN/IEC 60947-1 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
Product Certifications CCC CSA EAC UL
Mounting Mode Horizontal and vertical 35 mm symmetrical DIN rail)
Connections - Terminals screw-clamp terminals 1 0.00…0.01 in² (1…4 mm²) AWG 16...AWG 12)rigid screw-clamp terminals 2 0.00…0.01 in² (1…4 mm²) AWG 16...AWG 12)rigid screw-clamp terminals 1 0.00…0.01 in² (1.5…4 mm²) AWG 16...AWG 12)flexible without cable end screw-clamp terminals 2 0.00…0.01 in² (1.5…4 mm²) AWG 16...AWG 12)flexible without cable end screw-clamp terminals 1 0.00…0.01 in² (1…4 mm²) AWG 16...AWG 12)flexible with cable end screw-clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) AWG 16...AWG 14)flexible with cable end
Tightening Torque 15.05 lbf.in (1.7 N.m) flat Ø 6 mm 15.05 lbf.in (1.7 N.m) Philips No 2
Width 1.77 in (45 mm)
Height 4.76 in (121 mm)
Depth 4.53 in (115 mm)
Product Weight 0.56 lb(US) (0.255 kg)
Ambient Air Temp For Storage -13…158 °F (-25…70 °C)
Ambient Air Temp For Op 14…122 °F (-10…50 °C) without derating 122…140 °F (50…60 °C) with current derating
Relative Humidity 5…95 %
Operating Altitude 0...6561.68 ft (0...2000 m) without derating
IP Degree Of Protection IP20
Pollution Degree 2
Protective Treatment TC
Fire Resistance 1760 °F (960 °C) UL 94 1562 °F (850 °C) IEC 60695-2-1 1202 °F (650 °C) IEC 60695-2-12
Shock Resistance 15 gn 11 ms) IEC 60068-2-27
Vibration Resistance 1.5 mm peak to peak 3…13 Hz) IEC 60068-2-6 1 gn 13…200 Hz) IEC 60068-2-6
Electromagnetic Compatibility Electrostatic discharge immunity test, level 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) Radiated RF field immunity test, level 3 10 V/m)EN/IEC 61000-4-3) Fast transient immunity test, level 4 4 kV)EN/IEC 61000-4-4) Surge immunity test, level 3 2 kV)EN/IEC 61000-4-5) Surge immunity test, level 4 4 kV)EN/IEC 61000-4-5) Conducted RF disturbance immunity test 20 V)EN/IEC 61000-4-6)
Category 22352 - TESYS ISLAND LOAD CONTROLLERS
Discount Schedule I12
Nbr. Of Units In Pkg. 1
EU RoHs Directive Compliant
Mercury Free Yes
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews