This Harmony XENC1111 is a spring return contact block 1 NO front mounting, 30 or 40mm centres. It is part of the range Harmony XAC pendant control stations for diameter 22mm plastic signaling units. It is designed for single speed applications.
Add to Quote CataloguePart Number | XENC1111 |
---|---|
Country of Origin | CZ |
UPC | 785901643005 |
UPC11 | 78590164300 |
EAN | 3389110643008 |
Availability | S |
Lead Time | 36 |
UNSPSC | 39121561 |
ECCN | EAR99 |
HTs Code | 8536509065 |
Prop 65 | This product can expose you to chemicals including: Nickel compounds and Di-isodecyl phthalate (DIDP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CS2 |
Return Indicator | Yes |
Weight | 0.04 pound |
Range Of Product | Harmony XAC |
---|---|
Product Or Component Type | Contact block |
Component Name | XENC |
Electrical Circuit Type | Control circuit |
Contact Block Application | Single speed |
Contact Block Type | Single |
Type Of Operator | Spring return |
Product Compatibility | XACM XACB |
Mechanical Interlocking | Without mechanical interlock |
Contacts Type And Composition | 1 NO |
Mounting Of Block | Front mounting |
Contact Operation | Slow-break |
Connections - Terminals | Screw clamp terminals, 1 x 2.5 mm² with or without cable end Screw clamp terminals, 2 x 1.5 mm² with or without cable end |
Mechanical Durability | 1000000 cycles |
Contact Code Designation | A300 AC-15, Ue = 240 V, Ie = 3 A IEC 60947-5-1 appendix A Q300 DC-13, Ue = 250 V, Ie = 0.27 A IEC 60947-5-1 appendix A |
Ithe Cnvtl Enclosed Therm Crrt | 10 A |
Ui Rated Insulation Voltage | 500 V 3)IEC 60947-1 |
Uimp Rated Imp Wstd Voltage | 6 kV IEC 60947-1 |
Resistance Across Terminals | 25 MOhm |
Short-Circuit Protection | 10 A fuse protection cartridge gG |
Rated Opr Power In W | 42 W DC-13 1000000 cycles 60 cyc/mn 120 V 0.5 inductive IEC 60947-5-1 appendix C 45 W DC-13 1000000 cycles 60 cyc/mn 48 V 0.5 inductive IEC 60947-5-1 appendix C 60 W DC-13 1000000 cycles 60 cyc/mn 24 V 0.5 inductive IEC 60947-5-1 appendix C |
Rated Opr Power In VA | 140 VA AC-15 1000000 cycles 60 cyc/mn 24 V 50/60 Hz 0.5 inductive 385 VA AC-15 1000000 cycles 60 cyc/mn 48 V 50/60 Hz 0.5 inductive 455 VA AC-15 1000000 cycles 60 cyc/mn 230 V 50/60 Hz 0.5 inductive 525 VA AC-15 1000000 cycles 60 cyc/mn 127 V 50/60 Hz 0.5 inductive |
Terminals Description ISO n°1 | (13-14)NO |
Terminal Identifier | (13-14)NO (11-12)NC |
Product Weight | 0.04 lb(US) (0.02 kg) |
Standards | IEC 60947-5-1 EN 60947-5-1 CSA C22.2 No 14 |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Vibration Resistance | 15 gn 10…500 Hz)IEC 60068-2-6 |
Shock Resistance | 100 gn IEC 60068-2-27 |
Category | 22466 - PUSHBUTTON, ACCESSORIES |
Discount Schedule | CS2 |
GTIN | 00785901643005 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | CZ |
REACh Free Of SVHC | Yes |
EU RoHs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Toxic Heavy Metal Free | Yes |
Mercury Free | Yes |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Warranty | 18 months |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366