This hardware is an active power correction solution, from AccuSine familly, to help stabilize electrical networks by providing harmonic mitigation and power factor correction, and load balancing. In addition to 3-phase mitigation, it has the ability to compensate for neutral harmonic currents. This version is UL Type 1, and can be connected to a main unit. It is specified for a standard Root Mean Square output current rating of 60 Amps, 180 Amps neutral. The enclosure is wall mounted, allow cable entry from bottom and is delivered in RAL7035 light grey. This active power filter achieves above standards performance THDi less or equal to 3%, is certified to CE, IBC 2015, EAC, RCM. And is designed to IEC 62477-1, IEC 61000-6-2, IEC 61000-6-4 Class A, IEC 61439-1 and IEEE 519-2014. Up to 12 units in parallel per set of CT; any size unit combination possible (subject to network characteristics). Slave only. Frame exterior dimensions are 440 millimetres in width, 265 millimetres in depth, 960 millimetres in height and product weight 75 kg.
Add to Quote CataloguePart Number | PCSN060Y4N1E |
---|---|
EAN | 3606481813619 |
Availability | N |
Lead Time | 14 |
Discount Schedule | DE2C |
Depth | 10.4 inch |
Height | 56.7 inch |
Width | 17.5 inch |
Weight | 196 pound |
Range Of Product | AccuSine |
---|---|
Product Name | AccuSine PCSn |
Product Or Component Type | Active harmonic filter |
Network Type | 3P + N 3P |
Network Configuration | 3 or 4 wires |
Network Rated Voltage | 208…415 V AC |
Network Frequency | 50/60 Hz |
Maximum Permissible Voltage | 1.1 x Un |
Rms Output Current Rating | 60 A |
Reactive Power Rating | 21.6 kvar 208 V AC 50/60 Hz |
Operating Modes | Phase harmonic correction Neutral harmonic correction Mains current balancing Power factor correction |
Installation Location | Indoor |
Mounting Mode | Wall-mounted |
Protection Type | Without protection |
Heat Dissipation | Rear plenum with forced ventilation for high heat flow |
Electromagnetic Compatibility | Electromagnetic emission, class A EN 61000-6-4 Electromagnetic immunity EN 61000-6-2 |
Accessibility For Operation | Front |
Location Of Connection | Bottom |
Enclosure Degree Of Protection | UL type 1 |
Environmental Characteristic | Operating 3C2 IEC 60721-3-3 Operating 3S2 IEC 60721-3-3 Storage 3C3 IEC 60721-3-3 Storage 3S3 IEC 60721-3-3 |
Operating Altitude | <= 3280.84 ft (1000 m) 1 % per 100 m 0...4800 m |
Ambient Air Temp For Op | 32…104 °F (0…40 °C) 32…122 °F (0…50 °C) maximum with current derating of 2 % per °C above 40 °C |
Relative Humidity | 0…95 % non-condensing |
Pcba Protection | Conformal coated |
Standards | IEC 62477-1 IEC 61439-1 EN 61000-6-2 EN 61000-6-4 ISO 9001 IEEE 519-2014 UL 508 |
Product Certifications | CULus |
Ambient Air Temp For Storage | -4…140 °F (-20…60 °C) |
Product Weight | 196 lb(US) (88.90 kg) |
Height | 56.7 in (1440.18 mm) |
Width | 17.5 in (444.50 mm) |
Colour | Light gray RAL 7035) |
Depth | 10.4 in (264.16 mm) |
REACh Free Of SVHC | Yes |
EU RoHs Directive | Under investigation |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366