Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Multi 9 OV/UV + auto reset release – 2P – 32A
926232
Multi 9 OV/UV + auto reset release – 2P – 32A
Specifications
Part Number 926232
EAN 3606481340566
RoHS Compliant Yes
Depth 2.83 inch
Height 3.34 inch
Width 1.42 inch
Characteristics
Range Multi 9
Product Or Component Type Voltage release
Device Short Name CNV
Poles Description 2P
Ue Rated Operational Voltage 230 V AC 50 Hz between phase and neutral
Supply Voltage Limits 50…440 V AC, 1 phase
Ie Rated Operational Current 32 A
Ov/Uv Auto-Reset Complusive Delay Time Overvoltage 275 V 3…15 s) Overvoltage 300 V 1…5 s) Overvoltage 350 V 0.25…0.75 s) Overvoltage 400 V 0.1…0.2 s) Undervoltage 50...160 V 0.6…5 s) Lockout
Reset Automatic reset 25…35 s 253 V for overvoltage Automatic reset 25…35 s 195 V for undervoltage
Electric Clearance 0.05 in (1.2 mm)
Leakage Current 2 mA
Creepage Distance 5.6 mm
Uimp Rated Imp Wstd Voltage 4 kV between phases 4 kV between phase and neutral
Local Signalling Indicator light green, steady fault Indicator light green, flashing lock Indicator light red, steady operating
Time Delay 0...800 s on-delay
Function Available Real time voltage detection
Ui Rated Insulation Voltage 500 V
Rated Brking And Making Cap 256 A 242 V, cos phi = 0.85 12 times)
Icw Rated Short-Time Wstd Crrt 504 kA 4 s
Mounting Support DIN rail
Mounting Mode By clips
Cable Entry Bottom entry
Mounting Location Downstream
Installation Direction Horizontal Vertical
Use Category Indoor installation
9 mm Pitches 4
Height 3.34 in (84.8 mm)
Width 1.42 in (36 mm)
Depth 2.83 in (72 mm)
Colour Tint Clips light grey RAL 7035) Housing light grey RAL 7035)
Electrical Durability 12000 cycles 63 A 285 V AC 0.9
Mechanical Robustness Vibrations 3 Gn, 5…100 Hz) IEC 60068-2-6 Shocks 6 ms with protective package 30 Gn) IEC 60068-2-27 Free fall resistance 0.8m, without package
Service Life 10 year(s)
Electromagnetic Compatibility Electrostatic discharge immunity test 6 kV contact discharge)level 3 IEC 61000-4-2 Electrostatic discharge immunity test 8 kV air discharge)level 3 IEC 61000-4-2 Surge immunity test 2 kV common mode) IEC 61000-4-5 Surge immunity test 4 kV differential mode) IEC 61000-4-5 Electrical fast transient/burst immunity test 4 kV, 2.5 kHz, 5 kHz and 100 kHz IEC 61000-4-4 Immunity to conducted disturbances 10 V, 0.15...80 MHzlevel 3 IEC 61000-4-6 Immunity to conducted RF disturbances 10 V, 80...1000 MHz and 1400...6000 MHzlevel 3 IEC 61000-4-3 Conducted emissionclass B Radiated emissionclass B
Connections - Terminals Tunnel type terminals top or bottom 0.00…0.05 in² (1…35 mm²) rigid without cable end Tunnel type terminals top or bottom 0.00…0.04 in² (1…25 mm²) flexible with or without cable end
Tightening Torque Power circuit 30.98 lbf.in (3.5 N.m)
Standards JB/T 12762-2015
Product Certifications REACH
Directives 2002/95/EC - RoHS directive
IP Degree Of Protection IP40 on front face IEC 60529 IP20 B other parts IEC 60529
Pollution Degree 2
Operating Altitude <= 6561.68 ft (2000 m)
Ambient Air Temp For Op -13…131 °F (-25…55 °C)
Ambient Air Temp For Storage -40…176 °F (-40…80 °C)
Relative Humidity 0…75 % operating 0…95 % storage
Nbr. Of Units In Pkg. 1
Green Premium Status Green Premium product
EU RoHs Directive Compliant
Mercury Free Yes