Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Motor controller LTMR TeSys T – 24 V DC 27 A for Ethernet TCP/IP
LTMR27EBD
Motor controller LTMR TeSys T – 24 V DC 27 A for Ethernet TCP/IP
Specifications
Part Number LTMR27EBD
Country of Origin CN
UPC 785901633754
UPC11 78590163375
EAN 3389119404884
Availability S
Lead Time 33
UNSPSC 39122214
HTs Code 8537109170
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 4.82 inch
Height 2.40 inch
Width 3.58 inch
Weight 1.17 pound
Characteristics
Range TeSys
Product Name TeSys T
Device Short Name LTMR
Product Or Component Type Motor controller
Device Application Equipment monitoring and control
Measurement Current 1.35…27 A
[Us] Rated Supply Voltage 24 V DC
Current Consumption 56...127 mA
Supply Voltage Limits 20.4…26.24 V DC
Communication Port Protocol Modbus TCP/EtherNet/IP
Bus Type Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
Ui Rated Insulation Voltage 690 V EN/IEC 60947-1 690 V CSA C22.2 No 14 690 V UL 508
Uimp Rated Imp Wstd Voltage 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 0.8 kV communication circuit EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
Short-Circuit Withstand 100 kA EN/IEC 60947-4-1
Associated Fuse Rating 4 A gG output 0.5 A gG control circuit
Protection Type Earth-leakage protection Phase failure Thermal protection Overload Overload (long time) Reverse polarity protection Power factor variation Phase unbalance Thermal overload protection Load fluctuation Locked rotor
Ntw And Machine Diagnosis Type Remaining operating time before overload tripping Running hours counter/operating time Waiting time after overload tripping Phase fault and earth fault trip counters Fault recording Trip context information Trip history information Motor control command recording Starting current and time Event recording
Logic Input Number 6
Input Current 7 mA
Current State 0 Guaranteed Logic input < 5 V <= 15 mA 5 ms
Current State 1 Guaranteed Logic input < 15 V 2...15 mA 15 ms
Maximum Output Switching Frequency 2 Hz
Load Current 5 A 250 V AC logic output 5 A 30 V DC logic output
Permissible Power 480 VA AC-15), Ie = 2 A, 500000 cycles output) 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Operating Rate 1800 cyc/h
Contacts Type And Composition 1 NO + 1 NC fault signal 3 NO
Metering Type Phase current I1, I2, I3 RMS Average current Iavg Imbalance current Earth-fault current Temperature
Measurement Accuracy 5...15 % earth fault current internal measurement 1 % voltage 100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 1 % current 5 % active and reactive power
Overvoltage Category III
Connection Pitch 0.20 in (5.08 mm)
Connections - Terminals Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end Control circuit connector 2 0.00…0.00 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 2 0.00…0.00 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
Tightening Torque Control circuit 4.43…5.31 lbf.in (0.5…0.6 N.m) flat 0.12 in (3 mm)
Pollution Degree 3
Electromagnetic Compatibility Electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) Radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3) Fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4) Fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4) Voltage dips and interruptions immunity test 70 %, 500 ms)EN/IEC 61000-4-11) Conducted RF disturbances 10 V)EN/IEC 61000-4-6) Surges 0.5 kV)EN/IEC 61000-4-5) Surges 1 kV)EN/IEC 61000-4-5) Surges 1 kV)EN/IEC 61000-4-5) Surges 1 kV)EN/IEC 61000-4-5) Surges 2 kV)EN/IEC 61000-4-5) Surges 2 kV)EN/IEC 61000-4-5) Surges 4 kV)EN/IEC 61000-4-5)
Width 3.58 in (91 mm)
Height 2.40 in (61 mm)
Depth 4.82 in (122.5 mm)
Product Weight 1.17 lb(US) (0.53 kg)
Web Services Web server
Compatibility Code LTMR
Standards CSA C22.2 No 14 EN 60947-4-1 IACS E10 IEC 60947-4-1 UL 508
Product Certifications CCC BV KERI C-tick GL ATEX RINA CSA EAC UL NOM DNV LROS (Lloyds register of shipping) ABS RMRoS
Protective Treatment 12 x 24 hour cycles EN/IEC 60068-2-30 48 h EN/IEC 60070-2-11 TH EN/IEC 60068
Fire Resistance 1202 °F (650 °C) EN/IEC 60695-2-12 1760 °F (960 °C) UL 94
Ambient Air Temp For Op -4…140 °F (-20…60 °C)
Ambient Air Temp For Storage -40…176 °F (-40…80 °C)
Operating Altitude <= 6561.68 ft (2000 m) without derating
Mechanical Robustness Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
IP Degree Of Protection IP20
Category 22338 - SOLID STATE OVERLOAD RELAYS
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews