This Zelio RE48 timing relay can be set between 0.2 seconds and 300 hours, has an output rating of 5A, is 22.5mm wide and can be supplied with 24V to 240V AC. It is a plug-in device, meaning it is quick and easy to install with the need for tools. It also offers a sealable cover, simple and precise settings with rotary trimmers. This relay offers L, Li flashing functions. It is designed for both panel mouting or socket plug in, this gives more flexibility in designing installations and stocking spares. Single function timer for a simple integration in hard-wired logic schematics: ideal for refurbishment of old installations without using a PLC. Status display with 2 LEDs: visually inspect the status of you system without specialized tools.
Add to Quote CataloguePart Number | RE48ACV12MW |
---|---|
Country of Origin | ID |
UPC | 785901431060 |
UPC11 | 78590143106 |
EAN | 3389110649741 |
Availability | S |
Lead Time | 43 |
UNSPSC | 39121523 |
ECCN | EAR99 |
HTs Code | 8536490065 |
Prop 65 | This product can expose you to chemicals including: Nickel compounds and Di-isodecyl phthalate (DIDP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP2 |
Return Indicator | Yes |
Weight | 0.31 pound |
Range Of Product | Zelio Time |
---|---|
Product Or Component Type | Electronic timing relay |
Electrical Connection | Plug-in sub-base 11 |
Discrete Output Type | Relay |
Contacts Type And Composition | 2 C/O timed contacts, AgNi (cadmium free) |
Component Name | RE48A |
Time Delay Type | Li L |
Time Delay Range | 0.2...12 min 5...300 s 0.02...1.2 s 0.5...30 min 5...300 h 0.2...12 h 0.2...12 s 0.5...30 s 2...120 s 0.05...3 s 2...120 min 5...300 min 0.5...30 h 2...120 h |
[Us] Rated Supply Voltage | 24...240 V AC/DC 50/60 Hz |
Voltage Range | 0.85...1.1 Us AC 0.9...1.1 Us DC |
In Rated Current | 5 A |
Product Front Plate Size | 48 x 48 mm |
Control Type | Selector switch front panel |
Housing Material | Self-extinguishing |
Repeat Accuracy | +/- 0.2 % of the maximum setting value IEC 61812-1 |
Temperature Drift | +/- 0.02 %/°C of the maximum setting value IEC 61812-1 |
Voltage Drift | +/- 0.2 %/V of the maximum setting value 48...240 V +/- 1 %/V of the maximum setting value 24...48 V |
Setting Accuracy Of Time Delay | +/- 5 % of full scale 25 °C IEC 61812-1 |
Minimum Pulse Duration | 20 ms |
Reset Time | 25 ms on de-energisation |
Pick Up Duration | 55 ms |
On-Load Factor | 100 % |
Power Consumption In Va | 1.1 VA 24 V 4.8 VA 240 V |
Power Consumption In W | 0.5 W 24 V 1.7 W 240 V |
Breaking Capacity | 1250 VA |
Minimum Switching Current | 100 mA |
Maximum Switching Current | 5 A |
Maximum Switching Voltage | 250 V AC/DC |
Electrical Durability | 100000 cycles |
Mechanical Durability | 30000000 cycles |
Output Voltage | 240 V 5 A AC-12 30 V 2 A DC-13 240 V 1.5 A AC-15 |
Marking | CE |
Surge Withstand | 1 kV differential mode IEC 61000-4-5 level 3 2 kV common mode IEC 61000-4-5 level 3 |
Mounting Support | Base mounted: socket Panel mounted: system supplied with the product |
Local Signalling | Output relay state 1 LED yellow) Flashing: relay energised timing in progress LED indicator green) On steady: relay energised, no timing in progress LED indicator green) |
Product Weight | 0.31 lb(US) (0.14 kg) |
Humidity Drift | +/- 0.05 %/%RH of the maximum setting value IEC 61812-1 |
Immunity To Microbreaks | 10 ms |
Dielectric Strength | 1 kV 1 mA/1 minute IEC 61812-1 |
Prot Against Electric Shocks | 4 kV class III IEC 60664-1 4 kV class III IEC 61812-1 |
Standards | EN 50081-1/2 EN 50082-1/2 IEC 61812-1 93/68/EEC 89/336/EEC IEC 60669-2-3 73/23/EEC |
Product Certifications | GL UL C-tick CULus CSA |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Ambient Air Temp For Op | -4…122 °F (-20…50 °C) |
IP Degree Of Protection | IP40 IEC 60529 housing) IP50 IEC 60529 front face) |
Vibration Resistance | 0.35 mm 10…55 Hz)IEC 60068-2-6 |
Relative Humidity | 93 % without condensation IEC 60068-2-3 |
Resist Electrostatic Dischrg | 6 kV in contact EN/IEC 61000-4-2 level 3 8 kV in air EN/IEC 61000-4-2 level 3 |
Resist To Electromagn Fields | 9.14 V/m (10 V/m) 26 MHz to 1 GHz EN/IEC 61000-4-3 level 3 |
Resistance To Fast Transients | 2 kV EN/IEC 61000-4-4 level 4 capacitive connecting clip) 4 kV EN/IEC 61000-4-4 level 4 direct) |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366