This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The safety module provides 3 normally opened contacts and unlimited synchronisation time between inputs. It is a safety module with a rated supply voltage of 24V DC, an external supply current consumption of 100mA at 24V DC on power supply and a power consumption 0.2W at 5V DC, 3.6W at 24V DC. The main functions of this module are emergency stop, movable guard, multiple emergency stop, proximity sensor and electro-sensitive protection equipment (ESPE) monitoring. It is furnished with spring terminal for electrical connection. It is an IP20 rated product. Its dimensions are 43.7mm (Width) x 73mm (Depth) x 94mm (Height). It weighs 0.19kg. It is suitable for emergency stop, switch and safety light curtain monitoring applications. This product is certified by RCM, CSA, UL, TÜV, ANSI Haz Loc Class 1 Division 2, EAC. It supports wall mount using attached fasteners. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.
Add to Quote CataloguePart Number | TM3SAFL5RG |
---|---|
Country of Origin | DE |
UPC | 785901967156 |
UPC11 | 78590196715 |
EAN | 3606485393025 |
Availability | N |
Lead Time | 24 |
UNSPSC | 32151705 |
HTs Code | 8536509033 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | MSX |
Return Indicator | No |
Depth | 2.87 inch |
Height | 3.70 inch |
Width | 1.72 inch |
Weight | 0.42 pound |
Range Of Product | Modicon TM3 Safety |
---|---|
Product Or Component Type | Safety module |
Device Short Name | TM3SAFL |
Safety Module Application | For emergency stop, switch and safety light curtain monitoring |
Function Of Module | Emergency stop monitoring 2-channel wiring Monitoring of a movable guard with 2 switches and automatic start Monitoring of a movable guard Multiple emergency stop monitoring 2-channel wiring Proximity sensor monitoring PNP/PNP Monitoring of electro-sensitive protection equipment (ESPE) PNP/PNP |
Safety Level | Can reach PL d/category 3 EN/ISO 13849-1 2008 Can reach PL d/category 3 EN/ISO 13849-2 2012 Can reach SILCL 2 EN/IEC 62061 2005 Can reach SIL 2 EN/IEC 61508 2010 |
Safety Reliability Data | DC = 95 % EN/ISO 13849-1 PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A MTTFd = 500 years EN/ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A MTTFd = 85 years EN/ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 |
Synchro Time Between Inputs | Unlimited |
Connections - Terminals | Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals Captive spring terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals Captive spring terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals |
Output Type | Relay instantaneous opening, 3 NO, potential free |
Number Of Safety Circuits | 3 NO relay instantaneous opening |
Maximum Switching Voltage | 230 V AC-15 50 Hz relay instantaneous opening) 24 V DC-13 relay instantaneous opening) |
[Us] Rated Supply Voltage | 24 V - 15...20 % DC |
Power Consumption In W | 0.2 W 5 V DC 3.6 W 24 V DC |
Input Protection Type | Internal, electronic |
Uc Control Circuit Voltage | 24 V DC |
Cable Distance Between Devices | 98.43 ft (30 m) |
Breaking Capacity | 360 VA holding AC-15 B300 relay output 3600 VA inrush AC-15 B300 relay output |
Breaking Capacity | 4 A 24 V 50 ms DC-13 relay output |
Output Thermal Current | 6 A per relay relay output |
Ith Cnvtl Free Air Therm Crrt | 18 A |
Associated Fuse Rating | 4 A gG or gL relay output EN/IEC 60947-5-1 6 A fast blow relay output EN/IEC 60947-5-1 |
Minimum Output Current | 10 mA relay output |
Output Voltage | 10 V relay output |
Response Time On Input Open | 40 ms |
Ui Rated Insulation Voltage | 300 V 2)IEC 60647-5-1 |
Uimp Rated Imp Wstd Voltage | 4 kV III IEC 60647-5-1 |
Current Consumption | 100 mA 24 V DC external supply |
Local Signalling | User 8 LEDs green/red) |
Electrical Connection | Spring terminal |
Product Compatibility | Safety light curtains EN/IEC 61496-1 (type 4) |
Standards | EN/ISO 13849-1:2008 EN/ISO 13849-2:2012 EN/IEC 62061:2005 EN/IEC 61508:2010 EN/IEC 60947-5-1:2010 EN/IEC 61131-2:2007 EN/IEC 60204-1:2005 EN/IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012 |
Product Certifications | CSA 61010-2-201 (pending) RCM UL 61010-2-201 EAC ANSI Haz Loc Class 1 Division 2 (pending) CSA Haz Loc Class 1 Division 2 (pending) TÜV |
Marking | RCM REACH UL CSA EAC CE TÜV EFUP 10 |
Electromagnetic Compatibility | Electrostatic discharge immunity test 8 kV air discharge) EN/IEC 61000-4-2 Electrostatic discharge immunity test 6 kV contact discharge) EN/IEC 61000-4-2 Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) EN/IEC 61000-4-3 Susceptibility to electromagnetic fields 3 V/m 1.4 GHz...2 GHz) EN/IEC 61000-4-3 Susceptibility to electromagnetic fields 1 V/m 2 GHz...3 GHz) EN/IEC 61000-4-3 Magnetic field at power frequency 30 A/m 50...60 Hz) EN/IEC 61000-4-8 Electrical fast transient/burst immunity test 3 kV power lines (DC)) EN/IEC 61000-4-4 Electrical fast transient/burst immunity test 2 kV I/O) EN/IEC 61000-4-4 1.2/50 µs shock waves immunity test 1 kV power lines (DC)) EN/IEC 61000-4-5 Conducted RF disturbances 10 V 0.15...80 MHz) EN/IEC 61000-4-6 Radiated emission 40 dBµV/m 24 V)class A EN 55011 Radiated emission 47 dBµV/m 24 V)class A EN 55011 |
Mounting Support | Top hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715 wall mount using attached fasteners |
Height | 3.70 in (94 mm) |
Depth | 2.87 in (73 mm) |
Width | 1.72 in (43.7 mm) |
Product Weight | 0.42 lb(US) (0.19 kg) |
Standards | EN 60204-1 EN 1088/ISO 14119 EN/ISO 13850 EN/IEC 60947-1 EN/IEC 60947-5-1 |
Resist Electrostatic Dischrg | 8 kV in air EN/IEC 61000-4-2 6 kV on contact EN/IEC 61000-4-2 |
Resist To Electromagn Fields | 9.14 V/m (10 V/m) 80 MHz...1 GHz EN/IEC 61000-4-3 2.74 V/m (3 V/m) 1.4 GHz...2 GHz EN/IEC 61000-4-3 0.91 V/m (1 V/m) 2 GHz...3 GHz EN/IEC 61000-4-3 |
Resistance To Magnetic Fields | 98.43 A/m (30 A/m) 50/60 Hz EN/IEC 61000-4-8 |
Resistance To Fast Transients | 3 kV power lines (DC) DC)EN/IEC 61000-4-4 2 kV I/O linesEN/IEC 61000-4-4 |
Surge Withstand | 1 kV power lines (DC) differential mode EN/IEC 61000-4-5 DC 1 kV power lines (DC) common mode EN/IEC 61000-4-5 DC |
Resist To Conductd Disturbs | 10 V 0.15...80 MHz EN/IEC 61000-4-6 |
Electromagnetic Emission | Radiated emissions 50 dBµV/m class A 24 V DC)30…230 Hz IEC 61131-3 Radiated emissions 57 dBµV/m class A 24 V DC)230…1000 Hz IEC 61131-3 |
Ambient Air Temp For Op | 14…131 °F (-10…55 °C) horizontal installation |
Ambient Air Temp For Storage | -13…158 °F (-25…70 °C) |