Part Number | GWTUPS200 |
---|---|
Depth | 32.48 inch |
Height | 74.80 inch |
Width | 39.96 inch |
Weight | 2645.55 pound |
Presentation | Performance 3 phase power protection designed for flexibility in order to meet a wide range of requirements: from data centers to industrial and facilities applications. |
---|---|
Lead Time | Usually Ships within 2 Weeks |
Provided Equipment | Installation guide User Manual |
Bypass Wiring Configuration | 4 wire (3PH + N) 5 wire (3PH + N + G) |
Bypass Voltage Tolerance | +/-10% settable from +/-4/6/8 and 10% |
Max Bypass Input Current | 338 A |
Bypass Current Protection | 400 A |
Colour | Beige |
Depth | 32.48 in (82.5 cm) |
Height | 74.80 in (190 cm) |
Product Weight | 2645.55 lb(US) (1200 kg) |
Width | 39.96 in (101.5 cm) |
Network Frequency | 45...65 Hz |
Number Of Input Connectors | 1 Hard Wire 4-wire (3PH + N) 1 Hard Wire 5-wire (3PH + N + G) |
Input Voltage Limits | 323...437 V adjustable 380 V 340...460 V adjustable 400 V 357...477 V adjustable 415 V 177...239 V 208 V 340...460 V 400 V 408...552 V 480 V |
Inputvolt_Other | 400 V |
Maximum Input Current | 692 A |
Switching Current Capacity | 400 A |
Max Short Time Withstd Current | 16 kA |
Input Harmonic Distortion | Less than 7% for full load |
Input Protection Type | 3-pole breaker |
Input Voltage | 3 phase 3 phase 3 phase |
Rated Power In W | 160000 W |
Max Configurable Power In W | 160000 W |
Harmonic Distortion | Less than 2% |
Output Frequency | 50/60 Hz +/- 5 % sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal not synced 50 Hz +/- 0.1 % for 50 Hz nominal not synced |
Outputvolt_Other | 400 V |
Ups Type | Double Conversion Online |
Wave Type | Sine wave |
Output Connector Type | Hard Wire 5-wire (3PH + N + G) 1 Hard Wire 4-wire (3PH + N) 1 |
Output Voltage Tolerance | +/-1% static and +/- 5% at 100% load step |
Output Harmonic Distortion | < 2% linear load and < 3% non-linear load |
Output Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
Req Output Current Protection | 289 A |
Neutral Output Current | 433 A |
Bypass Type | Built-in Maintenance Bypass |
Output Voltage | 208 V 3 phase 480 V 3 phase 600 V 3 phase |
Product Certifications | CE LCIE TÜV |
Standards | EN/IEC 62040-2 EN/IEC 62040-3 EN/IEC 62040-1-1 IEC 61000-4-5 ISO 14001 ISO 9001 |
Ambient Air Temp For Op | 32…95 °F (0…35 °C) |
Relative Humidity | 20…80 % |
Operating Altitude | 0...3281 ft |
Ambient Air Temp For Storage | -13…104 °F (-25…40 °C) |
Storage Altitude | 0…30000 ft (0.00…9144.00 m) |
Acoustic Level | 68 dBA |
IP Degree Of Protection | IP20 |
Battery Type | External battery system |
Additional Information | Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage |