Part Number | XCPR2902G11 |
---|---|
Country of Origin | FR |
UPC | 389118158108 |
UPC11 | 38911815810 |
EAN | 3389118158108 |
Availability | N |
Lead Time | 20 |
UNSPSC | 39122213 |
ECCN | EAR99 |
HTs Code | 8536509055 |
Prop 65 | This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | T |
Return Indicator | No |
Depth | 1.18 inch |
Height | 2.56 inch |
Width | 1.22 inch |
Weight | 0.25 pound |
Range Of Product | OsiSense XC |
---|---|
Series Name | Standard format |
Product Or Component Type | Limit switch |
Device Short Name | XCPR |
Sensor Design | Compact |
Reset | With |
Body Type | Fixed |
Head Type | Plunger head |
Material | Plastic |
Body Material | Plastic |
Head Material | Zamak |
Fixing Mode | By the body |
Movement Of Operating Head | Linear |
Type Of Operator | Spring return roller plunger metal |
Type Of Approach | Lateral approach, 2 directions |
Cable Entry | 1 entry tapped for Pg 11 cable gland 0.35…0.47 in (9…12 mm) |
Number Of Poles | 2 |
Contacts Type And Composition | 1 NC + 1 NC |
Contact Operation | Snap action |
Switch Actuation | By 30° cam |
Electrical Connection | Screw-clamp terminals 1 x 0.34...2 x 1.5 mm² |
Contacts Insulation Form | Zb |
Positive Opening | With |
Positive Opening Min Force | 36 N |
Minimum Force For Tripping | 12 N |
Maximum Actuation Speed | 1.64 ft/s (0.5 m/s) |
Repeat Accuracy | 0.1 mm on the tripping points with 1 million operating cycles |
Contact Code Designation | A300, AC-15 (Ue = 240 V), Ie = 3 A 10 A EN/IEC 60947-5-1 appendix A Q300, DC-13 (Ue = 250 V), Ie = 0.27 A EN/IEC 60947-5-1 appendix A |
Ui Rated Insulation Voltage | 300 VUL 508 500 V 3)EN 60947-1 500 V 3)IEC 60947-1 300 VCSA C22.2 No 14 |
Resistance Across Terminals | 25 MOhm IEC 60255-7 category 3 |
Uimp Rated Imp Wstd Voltage | 6 kV IEC 60664 6 kV IEC 60947-1 |
Short-Circuit Protection | 10 A cartridge fuse gG |
Electrical Durability | 5000000 cycles, DC-13, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles, DC-13, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles, DC-13, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C |
Width | 1.22 in (31 mm) |
Height | 2.56 in (65 mm) |
Depth | 1.18 in (30 mm) |
Product Weight | 0.25 lb(US) (0.115 kg) |
Terminals Description ISO n°1 | (11-12)NC (21-22)NC |
Shock Resistance | 50 gn 11 ms IEC 60068-2-27 |
Vibration Resistance | 25 gn 10…500 Hz)IEC 60068-2-6 |
IP Degree Of Protection | IP66 IEC 60529 IP67 IEC 60529 |
IK Degree Of Protection | IK04 EN 50102 |
Overvoltage Category | Class II IEC 61140 Class II NF C 20-030 |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Protective Treatment | TC |
Product Certifications | UL CSA |
Standards | IEC 60204-1 IEC 60947-5-1 CSA C22.2 No 14 EN 60204-1 UL 508 EN 60947-5-1 |
Category | 22418 - LIMIT SWITCH,IEC,XCKP&XCKT |
Discount Schedule | T |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366