Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Limit switch XCKS – metal end plunger – 1NC+1NO – snap action – Pg13
XCKS101
Limit switch XCKS – metal end plunger – 1NC+1NO – snap action – Pg13
Specifications
Part Number XCKS101
Country of Origin FR
UPC 785901849995
UPC11 78590184999
EAN 3389110646887
Availability N
UNSPSC 39122213
ECCN EAR99
HTs Code 8536509055
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule T
Return Indicator No
Depth 1.46 inch
Height 4.09 inch
Width 1.57 inch
Weight 0.28 pound
Characteristics
Range Of Product OsiSense XC
Series Name Standard format
Product Or Component Type Limit switch
Device Short Name XCKS
Sensor Design Form B CENELEC EN 50041
Body Type Fixed
Head Type Plunger head
Material Plastic
Body Material Plastic
Head Material Plastic
Fixing Mode By the body
Movement Of Operating Head Linear
Type Of Operator Spring return plunger metal
Type Of Approach Vertical approach, 1 direction
Cable Entry 1 entry tapped for Pg 13.5 cable gland 0.35…0.47 in (9…12 mm)
Number Of Poles 2
Contacts Type And Composition 1 NC + 1 NO
Contact Operation Snap action
Switch Actuation On end
Electrical Connection Screw-clamp terminals 1 x 0.34...2 x 1.5 mm²
Contacts Insulation Form Zb
Number Of Steps 1
Positive Opening With
Positive Opening Min Force 30 N
Minimum Force For Tripping 15 N
Minimum Actuation Speed 0.01 m/min
Maximum Actuation Speed 1.64 ft/s (0.5 m/s)
Repeat Accuracy 0.05 mm on the tripping points with 1 million operating cycles
Contact Code Designation A300, AC-15 (Ue = 240 V), Ie = 3 A EN/IEC 60947-5-1 appendix A Q300, DC-13 (Ue = 250 V), Ie = 0.27 A EN/IEC 60947-5-1 appendix A
Ithe Cnvtl Enclosed Therm Crrt 10 A AC
Ui Rated Insulation Voltage 300 VUL 508 500 V 3)IEC 60947-1 300 VCSA C22.2 No 14
Resistance Across Terminals 25 MOhm IEC 60255-7 category 3
Uimp Rated Imp Wstd Voltage 6 kV IEC 60664 6 kV IEC 60947-1
Short-Circuit Protection 10 A cartridge fuse gG
Electrical Durability 5000000 cycles, DC-13, inductive, 120 V, 4 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles, DC-13, inductive, 24 V, 10 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C 5000000 cycles, DC-13, inductive, 48 V, 7 W 60 cyc/mn 0.5 IEC 60947-5-1 appendix C
Mechanical Durability 25000000 cycles
Width 1.57 in (40 mm)
Height 4.09 in (104 mm)
Depth 1.46 in (37 mm)
Product Weight 0.28 lb(US) (0.125 kg)
Terminals Description ISO n°1 (21-22)NC (13-14)NO
Shock Resistance 40 gn 11 ms IEC 60068-2-27
Vibration Resistance 25 gn 10…500 Hz)IEC 60068-2-6
IP Degree Of Protection IP67 IEC 60529 IP66 IEC 60529
IK Degree Of Protection IK05 EN 50102
Electrical Shock Protect Class Class II IEC 61140 Class II NF C 20-030
Overvoltage Category Class II IEC 61140 Class II NF C 20-030
Ambient Air Temp For Op -13…158 °F (-25…70 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Protective Treatment TC
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews