Inductive sensor hazardous area – 26x26x13 – Sn 10mm – NO – cable 10m
XS7E1A1PAL10EX
Inductive sensor hazardous area – 26x26x13 – Sn 10mm – NO – cable 10m
Specifications
Part Number XS7E1A1PAL10EX
Country of Origin FR
UPC 389118306660
UPC11 38911830666
EAN 3389118306660
Availability N
Lead Time 24
ECCN EAR99
HTs Code 8536507000
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule DS2
Return Indicator No
Depth 0.51 inch
Height 1.57 inch
Width 1.02 inch
Characteristics
Range Of Product OsiSense XS ATEX D
Series Name General purpose
Sensor Type Inductive proximity sensor
Device Application ATEX dust
Sensor Name XS7
Sensor Design Flat form 26 x 26 x 13
Size 13 mm
Body Type Fixed
Flush Mountability Flush mountable
Material Plastic
Enclosure Material PBT
Sn Nominal Sensing Distance 0.39 in (10 mm)
Type Of Output Signal Discrete
Wiring Techniquees 3-wire
Discrete Output Function 1 NO
Output Circuit Type DC
Discrete Output Type PNP
Electrical Connection Cable
Cable Length 32.81 ft (10 m)
Us Rated Supply Voltage 12...24 V DC reverse polarity protection
Switching Capacity In Ma <= 100 mA DC overload and short-circuit protection
IP Degree Of Protection IP68 double insulation IEC 60529
Detection Face Frontal
Front Material PBT
Sensing Range > 0.31...0.59 in (> 8...15 mm)
Operating Zone 0.00…0.31 in (0…8 mm)
Differential Travel 1...15% of Sr
Cable Composition 3 x 0.34 mm²
Wire Insulation Material PvR
Status Led Output state 1 LED yellow)
Supply Voltage Limits 10…36 V DC
Residual Current 0.5 mA open state
Switching Frequency <= 1000 Hz
Voltage Drop <2 V closed)
Current Consumption <= 10 mA no-load
Delay First Up 10 ms
Delay Response 2 ms
Delay Recovery 6 ms
Marking II2 D-Ex tb IIIC T90°C Db IP67
Depth 0.51 in (13 mm)
Height 1.57 in (40 mm)
Width 1.02 in (26 mm)
Environmental Characteristic Hazardous location
Standards EN/IEC 60079-0 EN/IEC 60079-31
Directives 94/9/EC - ATEX directive
Product Certifications INERIS 06ATEX0065X
Ambient Air Temp For Op -13…158 °F (-25…70 °C)
Ambient Air Temp For Storage -40…185 °F (-40…85 °C)
Vibration Resistance 25 gn +/- 2 mm 10…55 Hz)IEC 60068-2-6
Shock Resistance 50 gn 11 ms IEC 60068-2-27