This multi-circuit power meter is part of the PowerLogic EM4000 Series. This compact multi-circuit energy meter enables reliable metering of building electrical loads with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for departmental metering applications and M&V within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 80 mA solid core current transformers. Designed for 277 (phase neutral) or 480 volts (phase phase) networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 305 mm in height and 55 mm in depth ; for 4 kg.
Brand: Square D
Add to Quote CataloguePart Number | METSEEM408016 |
---|---|
Country of Origin | CA |
Availability | N |
Lead Time | 47 |
UNSPSC | 40151552 |
ECCN | EAR99 |
HTs Code | 9030840000 |
Prop 65 | This product can expose you to chemicals which are known to the State of California to cause Carcinogen and Reproductive harm.For more information go to www.p65warnings.ca.gov |
Discount Schedule | PL1 |
Return Indicator | No |
Depth | 2.17 inch |
Height | 13.19 inch |
Width | 12.01 inch |
Weight | 8.82 pound |
Range | PowerLogic |
---|---|
Product Or Component Type | Multi-circuit energy meter |
Product Name | PowerLogic EM4000 |
Device Short Name | EM4080 |
Power Monitoring | Basic instrumentation |
Energy Management | Sub billing and cost allocation Billing analysis |
Device Application | Sub billing |
Power Quality Analysis | compliance monitoring |
Type Of Measurement | Current per phase, rms Voltage per phase, rms Negative reactive energy Apparent energy Pulse count Active and reactive power Apparent power Positive active energy Positive reactive energy Negative active energy |
[Us] Rated Supply Voltage | 120 V AC 60 Hz |
Network Frequency | 60 Hz |
Sampling Rate | 256 samples/cycle |
Display Type | Backlit LCD |
Messages Display Capacity | 2 lines of 16 characters |
Current Transformer Input | 24 solid core CT 80 mA single pole 12 solid core CT 80 mA single phase 8 solid core CT 80 mA three phase |
Measurement Voltage | 80…480 V without PTs 480…999000 V with external PTs |
Measurement Accuracy | +/- 0.5 % of the measuring range |
Number Of Inputs | 2 pulse |
Communication Port Protocol | BACnet IP FTP HTTP Modbus TCP/IP SNTP |
Communication Port Support | RJ45 Ethernet RS485 |
Communication Of Data | Negative active energy Positive active energy Voltage Positive reactive energy Apparent energy Negative reactive energy |
Mounting Mode | Wall mount |
Device Mounting | Wall mounted |
Enclosure Type | NEMA type 1 |
Type Of Installation | Enclosed outdoor Indoor installation |
Relative Humidity | 90 % 104 °F (40 °C) |
Pollution Degree | 2 |
Ambient Air Temp For Op | -40…158 °F (-40…70 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) |
Operating Altitude | <= 9842.52 ft (3000 m) |
Standards | IEC 6100-4-5 ICES-003 FCC Part 15 class B CSA C22.2 No 61010-1 EN 55022 ANSI/TIA-968-A : 2002 CSA C22.2 No 61010-1-4 |
Product Certifications | UL |
Width | 12.01 in (30.5 cm) |
Depth | 2.17 in (5.5 cm) |
Height | 13.19 in (33.5 cm) |
Product Weight | 8.82 lb(US) (4 kg) |
Category | 09796 - POWERLOGIC EM40/48 HARDWARE |
Discount Schedule | PL1 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | CA |
EU RoHs Directive | Not compliant |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |