EM4000 multi-circuit energy meter, 24 x 333 mV inputs, 277V control power 60 Hz
METSEEM403316
EM4000 multi-circuit energy meter, 24 x 333 mV inputs, 277V control power 60 Hz

This multi-circuit power meter is part of the PowerLogic EM4000 Series. This compact multi-circuit energy meter enables reliable metering of building electrical loads with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for departmental metering applications and M&V within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 0.333 volt split or solid core current transducer. Designed for 277 (phase neutral) or 480 volts (phase phase) networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 305 mm in height and 55 mm in depth ; for 4 kg.

Brand: Square D

Add to Quote Catalogue
Specifications
Part Number METSEEM403316
Country of Origin CA
UPC 785901755159
UPC11 78590175515
EAN 0785901755159
Availability N
Lead Time 3
UNSPSC 40151552
ECCN EAR99
HTs Code 9030840000
Prop 65 This product can expose you to chemicals which are known to the State of California to cause Carcinogen and Reproductive harm.For more information go to www.p65warnings.ca.gov
Discount Schedule PL1
Return Indicator No
Depth 2.17 inch
Height 13.19 inch
Width 12.01 inch
Weight 8.82 pound
Characteristics
Range PowerLogic
Product Or Component Type Multi-circuit energy meter
Product Name PowerLogic EM4000
Device Short Name EM4033
Power Monitoring Basic instrumentation
Energy Management Sub billing and cost allocation Billing analysis
Device Application Sub billing
Power Quality Analysis compliance monitoring
Type Of Measurement Current per phase, rms Voltage per phase, rms Negative reactive energy Apparent energy Pulse count Active and reactive power Apparent power Positive active energy Positive reactive energy Negative active energy
[Us] Rated Supply Voltage 120 V AC 60 Hz
Network Frequency 60 Hz
Sampling Rate 256 samples/cycle
Display Type Backlit LCD
Messages Display Capacity 2 lines of 16 characters
Current Transformer Input 24 solid core CT 0.333 V single pole 12 solid core CT 0.333 V single phase 8 solid core CT 0.333 V three phase 24 split core CT 0.333 V single pole 12 split core CT 0.333 V single phase 8 split core CT 0.333 V three phase
Measurement Voltage 80…480 V without PTs 480…999000 V with external PTs
Measurement Accuracy +/- 0.5 % of the measuring range
Number Of Inputs 2 pulse
Communication Port Protocol BACnet IP FTP HTTP Modbus TCP/IP SNTP
Communication Port Support RJ45 Ethernet RS485
Communication Of Data Voltage Positive active energy Positive reactive energy Negative reactive energy Apparent energy Negative active energy
Mounting Mode Wall mount
Device Mounting Wall mounted
Enclosure Type NEMA type 1
Type Of Installation Indoor installation Enclosed outdoor
Relative Humidity 90 % 104 °F (40 °C)
Pollution Degree 2
Ambient Air Temp For Op -40…158 °F (-40…70 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Operating Altitude <= 9842.52 ft (3000 m)
Standards ANSI/TIA-968-A : 2002 EN 55022 FCC Part 15 class B IEC 6100-4-5 ICES-003 CSA C22.2 No 61010-1-4 CSA C22.2 No 61010-1
Product Certifications UL
Width 12.01 in (30.5 cm)
Depth 2.17 in (5.5 cm)
Height 13.19 in (33.5 cm)
Product Weight 8.82 lb(US) (4 kg)
Category 09796 - POWERLOGIC EM40/48 HARDWARE
Discount Schedule PL1
GTIN 00785901755159
Nbr. Of Units In Pkg. 1
Country Of Origin CA
EU RoHs Directive Not compliant
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.