Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Electronic timer module – type on delay – 1.5….30 s – 24….250 V DC/AC
LA4DT2U
Electronic timer module – type on delay – 1.5….30 s – 24….250 V DC/AC

TeSys D electronic timer module for LC1D09-D38, LC1D40A-D80A, LC1D80-D150 (3P) contactors. To be used with 24-250V AC control circuit voltages, it provides a manual ajustable on-delay time 1.5 to 30 sec. The time delay period is signalling by LED. Mounting on contactors LC1D09-D38 using adapter LAD4BB, on contactors LC1D40A-D80A using adpater LAD4BB3, on contactors LC1D80-D150 (3P) directly on coil terminals. Multi standards certified (IEC, UL, CSA), it conforms to RoHS/REACh regulation.

Add to Quote Catalogue
Specifications
Part Number LA4DT2U
Country of Origin TN
UPC 785901260998
UPC11 78590126099
EAN 3389110236460
Availability S
Lead Time 3
UNSPSC 39121529
ECCN EAR99
HTs Code 8536490050
RoHS Compliant Yes
Discount Schedule I12
Return Indicator Yes
Weight 0.09 pound
Characteristics
Range TeSys
Product Or Component Type Serial timer modules
Device Short Name LA4DT
Poles Description 3P
Product Compatibility 3 poles LC1D09...D38 4 poles LC1DT20...DT40
Mounting Location Top
[Uc] Control Circuit Voltage 24...250 V AC 50/60 Hz 24...250 V DC
Ctrl Circuit Voltage Limits By mechanical contact 0.8...1.1 Uc
Ui Rated Insulation Voltage 250 V IEC 60947-1
Connections - Terminals Control circuit connector 1 0.00 in² (1 mm²)flexible with cable end Control circuit connector 1 0.00 in² (1 mm²)solid with cable end Control circuit connector 2 0.00 in² (2.5 mm²)flexible without cable end Control circuit connector 2 0.00 in² (2.5 mm²)solid without cable end
Electrical Durability 30 Mcycles
Timer Type On delay
Time Delay Range 1.5...30 s
Reset Time 150 ms during time delay 50 ms after time delay
Local Signalling Illuminates during time delay by LED
Ures Residual Voltage 3.3 V
Product Weight 0.09 lb(US) (0.04 kg)
Standards IEC 60255-5
Product Certifications CSA UL
IP Degree Of Protection IP2x VDE 0106
Protective Treatment TH IEC 60068
Ambient Air Temp For Op -13…131 °F (-25…55 °C)
Ambient Air Temp Around Device -13…158 °F (-25…70 °C)
Ambient Air Temp For Storage -40…176 °F (-40…80 °C)
Protection Type Built-in by varistor
Heat Dissipation 2 W 50/60 Hz
Immunity To Microbreaks 10 ms during time delay 2 ms after time delay
Category 22341 - CONTACTOR,D,K,&F ACCESS
Discount Schedule I12
GTIN 00785901260998
Nbr. Of Units In Pkg. 1
Country Of Origin TN
Green Premium Status Green Premium product
REACh Free Of SVHC Yes
EU RoHs Directive Compliant
Toxic Heavy Metal Free Yes
Mercury Free Yes
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Warranty 18 months
Documents