Part Number | BJL26080LU |
---|---|
UPC | 606481194138 |
UPC11 | 60648119413 |
EAN | 3606481194138 |
UNSPSC | 39121601 |
Prop 65 | This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Return Indicator | No |
Depth | 3.15 inch |
Height | 5.39 inch |
Width | 2.13 inch |
Weight | 1.70 pound |
Range | PowerPact |
---|---|
Product Name | PowerPact B |
Device Short Name | BJ 080 |
Product Or Component Type | Circuit breaker |
Device Application | Distribution |
In Rated Current | 80 A |
Number Of Poles | 2P |
Protected Poles Description | 2t |
Control Type | Toggle |
Rating Code | J |
Breaking Capacity | 100 kA 208Y/120 V AC 50/60 Hz UL 489 100 kA 240 V AC 50/60 Hz UL 489 65 kA 480/277 V AC 50/60 Hz UL 489 65 kA 480 V AC 50/60 Hz UL 489 25 kA 600Y/347 V AC 50/60 Hz UL 489 50 kA 250 V DC UL 489 |
Ue Rated Operational Voltage | 690 V AC 50/60 Hz UL 489 |
Ics Rated Service Breaking Cap | 100 kA 220...240 V AC 50/60 Hz IEC 60947-2 25 kA 500...525 V AC 50/60 Hz IEC 60947-2 2.5 kA 690 V AC 50/60 Hz IEC 60947-2 65 kA 380...415 V AC 50/60 Hz IEC 60947-2 65 kA 440 V AC 50/60 Hz IEC 60947-2 |
Uimp Rated Imp Wstd Voltage | 8 kV IEC 60947-2 |
Ui Rated Insulation Voltage | 800 V IEC 60947-2 |
Trip Unit Technology | Thermal-magnetic |
Trip Unit Name | TM-D |
Suitability For ISOlation | Yes IEC 60947-2 |
Utilisation Category | Category A |
Mechanical Durability | 15000 cycles IEC 947-1 Annex K ed 5.2 |
Electrical Durability | 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In |
Connection Pitch | 1.06 in (27 mm) |
Local Signalling | Presence of auxiliary contacts flag green) |
Mounting Mode | Clip-on 35 mm symmetrical DIN rail) By screws plate) |
Electrical Connection | Everlink lug line Everlink lug load |
Awg Gauge | AWG 6...AWG 2/0 fine stranded aluminium/copper AWG 14...AWG 3/0 rigid or stranded aluminium/copper |
Tightening Torque | 44.25 lbf.in (5 N.m) 0.00…0.02 in² (2.5…16 mm²) AWG 14...AWG 4) 79.66 lbf.in (9 N.m) 0.04…0.15 in² (25…95 mm²) AWG 3...AWG 3/0) |
Number Of Slots | 1 auxiliary switch OF plug-in) 1 voltage release MN or MX plug-in) |
Power Wire Stripping Length | 0.79 in (20 mm) |
Color | Gray RAL 7016) |
9 mm Pitches | 6 |
Height | 5.39 in (137 mm) |
Width | 2.13 in (54 mm) |
Depth | 3.15 in (80 mm) |
Product Weight | 1.70 lb(US) (0.769 kg) |
Quantity Per Set | Set of 1 |
Continuous Current Rating | 80 % |
Quality Labels | CE |
Standards | EN/IEC 60947-5-1 UL 489 CSA C22.2 No 5 GB 14048.2 EN/IEC 60947-2 NEMA AB1 NMX J-266 |
Product Certifications | UL IEC CCC EAC CSA NOM |
IP Degree Of Protection | Front cover IP40 IEC 60529 |
IK Degree Of Protection | IK07 IEC 62262 |
Pollution Degree | 3 IEC 60947-1 |
Ambient Air Temp For Op | -13…158 °F (-25…70 °C) |
Ambient Air Temp For Storage | -58…185 °F (-50…85 °C) |
Operating Altitude | 6561.68 ft (2000 m) without derating 5000 m with derating |
Category | 01132 - BJ/BK UNIT MOUNT BREAKER/SWITCH |
Discount Schedule | DE2 |
GTIN | 03606481194138 |
Nbr. Of Units In Pkg. | 1 |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366