Part Number | LV839141 |
---|---|
UNSPSC | 39121601 |
Depth | 16.80 inch |
Height | 17.28 inch |
Width | 17.49 inch |
Product Name | Masterpact MTZ2 |
---|---|
Device Short Name | MTZ2 16 H |
Product Or Component Type | Circuit breaker |
Device Application | Protection |
Poles Description | 3P |
Network Type | AC |
Network Frequency | 50/60 Hz |
Rating Code | H |
Control Type | Push-button |
Mounting Mode | Drawout |
Mounting Support | Base plate Rails |
In Rated Current | 1600 A 104 °F (40 °C) |
Circuit Breaker Ct Rating | 1600 A |
Performance Level | 100 kA Icu 240 V AC 50/60 Hz UL 489 100 kA Icu 480 V AC 50/60 Hz UL 489 85 kA Icu 600 V AC 50/60 Hz UL 489 |
Mechanical Durability | 12500 cycles ANSI C37.50 |
Electrical Durability | 2800 cycles ANSI C37.50 |
Connection Pitch | 4.53 in (115 mm) |
Icw Rated Short-Time Wstd Crrt | 65 kA 0.5 s UL 489 |
Integ Instant Protection | 81…99 kA |
Rated Brking And Making Cap | 90 kA |
Maximum Breaking Time | 25…30 ms |
Closing Response Time | 70 ms |
Height | 17.28 in (438.8 mm) |
Width | 17.49 in (444.3 mm) |
Depth | 16.80 in (426.8 mm) |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366