This hardware is an active power correction solution, from AccuSine familly, to help stabilize electrical networks by providing harmonic mitigation and power factor correction, and load balancing. It is specifically designed for harsh electrical conditions, for heavy industrial applications including mission critical environments. This version is ingress protection IP54 and can be connected on Low Voltage networks rated 208 Volt to 240 Volt. It is specified for a standard Root Mean Square output current rating of 300 Amps. The enclosure is floor standing, allow cable entry from top or bottom and is delivered in RAL7035 light grey. This active power filter achieves above standards performance THDi less or equal to 3%, is certified to CE, UL, IBC 2015 AC156, EAC, RCM. And is designed to IEC 62477-1, IEC 61000-6-2, IEC 61000-6-4, IEC 61439-1, UL508 and IEEE 519-2014. Up to 10 units of different ratings can be paralleled, to achieve a maximum compensation of 3000A per CT set. Frame exterior dimensions are 900 millimetres in width, 600 millimetres in depth, 2100 millimetres in height and product weight 436 kg.
Brand: Square D
Add to Quote CataloguePart Number | PCSP300D2IP54 |
---|---|
Country of Origin | US |
Availability | N |
Lead Time | 70 |
UNSPSC | 83101808 |
ECCN | EAR99 |
HTs Code | 8504409550 |
RoHS Compliant | Yes |
Discount Schedule | DE2C |
Return Indicator | No |
Depth | 23.62 inch |
Height | 82.68 inch |
Width | 35.43 inch |
Weight | 892.87 pound |
Range Of Product | AccuSine |
---|---|
Product Name | AccuSine PCS+ |
Product Or Component Type | Active harmonic filter |
Network Type | 3P |
Network Configuration | 3 or 4 wires |
Network Rated Voltage | 208…240 V AC |
Network Frequency | 50/60 Hz +/- 3 Hz auto sensing |
Maximum Permissible Voltage | 1.1 x Un |
Neutral Correction | Not provided |
Rms Output Current Rating | 300 A |
Reactive Power Rating | 124.7 kvar 240 V AC 50/60 Hz |
Operating Modes | Harmonic cancellation Power factor correction Mains current balancing |
Installation Location | Indoor |
Enclosure Mounting | Floor-standing |
Protection Type | Circuit breaker protection |
Disconnect Type | Door-interlocked with rotary handle |
Interrupt Capacity | 200 kA |
Heat Dissipation | Rear plenum with forced ventilation for high heat flow |
Electromagnetic Compatibility | Conducted EMC, class A EN 61000-6-4 |
Accessibility For Operation | Front |
Location Of Connection | Top or bottom |
Enclosure Degree Of Protection | IP54 |
Environmental Characteristic | Operating 3C2 IEC 60721-3-3 Operating 3S2 IEC 60721-3-3 Storage 3C3 IEC 60721-3-3 Storage 3S3 IEC 60721-3-3 |
Operating Altitude | <= 3280.84 ft (1000 m) 1 % per 100 m |
Ambient Air Temp For Op | 32…104 °F (0…40 °C) 32…122 °F (0…50 °C) maximum with current derating of 2 % per °C |
Relative Humidity | 0…95 % |
Pcba Protection | Conformal coated |
Standards | CSA C22.2 No 14 CSA C22.2 No 60947-1-07 UL 508 EN 61000-6-4 UL 60947-1 EN 60439-1 |
Product Certifications | RCM ABS CULus CE |
Ambient Air Temp For Storage | -4…140 °F (-20…60 °C) |
Product Weight | 892.87 lb(US) (405 kg) |
Height | 82.68 in (2100 mm) |
Width | 35.43 in (900 mm) |
Colour | Light gray RAL 7035) |
Depth | 23.62 in (600 mm) |
Category | 00089 - ACTIVE FILTERS |
Discount Schedule | DE2C |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | US |
Green Premium Status | Green Premium product |
REACh Free Of SVHC | Yes |
EU RoHs Directive | Compliant |
Toxic Heavy Metal Free | Yes |
Mercury Free | Yes |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |