Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
4 adapter boards – advanced + ethernet – full power and energy on all circuits
BCPMSCE2S
4 adapter boards – advanced + ethernet – full power and energy on all circuits

This is an integrated solution for monitoring multi-circuits and mains by using a single meter. The meter is designed for retrofit and is used for critical power operations in data centres and energy management in buildings. It offers class 1 (1 %) power and energy system accuracy (including 50A, 100A or 200A split-core current transformers) on all branch channels. The BCPM allow the monitoring of both the branch circuits and mains values, incoming power and energy for a maximum of 84 circuits. All to provide information on the complete Power Distribution Unit. Full alarming capabilities ensure that potential issues are dealt with before they become problems. Communication enabled with serial connection for either Modbus RTU or BACnet MS/TP, and an Ethernet connection for Modbus TCP, BACnet IP and SNMP. The meter need to be powered by a 100V AC to 277V AC supply source. This version is for 84 circuits, but do not include branch current transformers nor ribbon. The device dimensions are 353mm in width, 253mm in height, 71mm in depth and weight 1.5 kilograms.

Brand: Veris Industries

Add to Quote Catalogue
Specifications
Part Number BCPMSCE2S
Availability N
Lead Time 15
UNSPSC 41113630
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
Discount Schedule PL1
Return Indicator No
Height 5.75 inch
Width 11.34 inch
Weight 3.31 pound
Characteristics
Range PowerLogic
Product Name PowerLogic BCPMSC
Product Or Component Type Multi-circuit energy meter
Device Short Name BCPMSCE
Model Type Advanced + ethernet
Power Monitoring Basic instrumentation
Energy Management Sub billing and cost allocation
Device Application Sub billing
Power Quality Analysis voltage sag and swell detection
Type Of Measurement Voltage Current Frequency Active power Power factor Active energy
[Us] Rated Supply Voltage 90...277 V AC 50/60 Hz +/- 1 %
Network Frequency 50 Hz 60 Hz
Current Transformer Input current 1 V 84 current 0.333 V
Update Time 1.8 s
Measurement Voltage 90…277 V phase to neutral 150…480 V phase to phase
Measurement Accuracy Branch current 2 % 0.25…2 A Branch current 2 % 2…100 A Mains current 2 % 1…100 % Mains current 2 % 2…100 % Voltage 2 % 90…277 V
Sampling Rate 256 samples/cycle
Provided Equipment 4 x adapter board 0 x current transformer
Communication Port Protocol Modbus RTU BACnet IP BACnet MS/TP Modbus TCP SNMP v2
Communication Port Support RS485 Ethernet
Communication Of Data Under voltage alarm High current alarm High-high current alarm Low-low current alarm Over voltage alarm Low current alarm
Mounting Mode Clip-on
Mounting Support Board
Relative Humidity 95 %
Ambient Air Temp For Op 32…140 °F (0…60 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Operating Altitude 9842.52 ft (3000 m)
Standards ANSI C12.1 EN 61010 IEC 61010-1
Product Certifications UL 508
Width 11.34 in (288 mm)
Height 5.75 in (146 mm)
Product Weight 3.31 lb(US) (1.5 kg)
Category 09793 - PLOGIC BRANCH CIRCUIT BCPM & MCM
Discount Schedule PL1
Nbr. Of Units In Pkg. 1
EU RoHs Directive Compliant
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.